User guide

54
operating and commissioning
Type 8025 / 8035
9.6.6. Configuring the relays
This parameter makes it possible to set the switching thresholds and the operating behaviour, inverted or not, of each relay.
Enter values such as 1- 1+ and/or 2- 2+.
Both relays work in an hysteresis operating.
RELAy
FiLtER
2-= 0000
2+ = 0000
1+ = 0000
1+ = 0010
2+ = 0044
1-= 0000
iNv NO
2-= 0040
1-= 0008
iNv yES
ENTER
0......9
0......9
ENTER
ENTER
ENTER
0......9
ENTER
0......9
ENTER
iNv NO
iNv yES
0......9
0......9
Enter a flow rate value, associated to
the high threshold of relays 1, in the unit
chosen in the "UNIT" parameter.
Confirm.
ENTER
Choose the sense of operating,
inverted or not inverted.
Confirm
Choose the sense of operating,
inverted or not inverted.
Confirm.
Enter a flow rate value, associated to the low threshold of
relays 1, in the unit chosen in the "UNIT" parameter.
Confirm.
Enter a flow rate value, associated to
the low threshold of relays 2, in the unit
chosen in the "UNIT" parameter.
Confirm.
Enter a flow rate value, associated to
the high threshold of relays 2, in the unit
chosen in the "UNIT" parameter.
Confirm.
Fig. 61: Configuration of the relays threshold in hysteresis operating
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to
save the settings and go back to the Process level.
English