User guide

57
operating and commissioning
Type 8025 / 8035
9.7.2. Adjusting the SPAN of the current output
This parameter makes it possible to adjust the 20 mA current value transmitted on the 4-20 mA output.
Connect a multimeter into the measurement loop.
The device generates a 20 mA current.
Measure the current given on the 4-20 mA output using a
multimeter.
Enter the value displayed by the multimeter. The permitted span
range is 15 to 21,50 mA.
Confirm.
SPAN
FREqUENC
ENTER
ENTER
SP= 19.90
SP= 20.00
0......9
Fig. 67: Adjustment of the SPAN
If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press
ENTER
to save the
settings and go back to the Process level.
9.7.3. Reading the rotational frequency of the paddle wheel
FREqUENC 195.3 hz
FLOw
ENTER
ENTER
Fig. 68: Diagram of the "FREQUENC." parameter of the Test menu
If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press
ENTER
to save the
settings and go back to the Process level.
9.7.4. Checking the outputs behaviour
This parameter makes it possible to simulate a flow rate in order to check that the outputs are behaving as expected by the
configuration made.
Enter a flow rate value, in the unit chosen in the "UNIT" parameter.
Confirm by pressing the
ENTER
key. the display returns on the
"FLOW" parameter.
Check that the outputs are behaving as expected.
To test another value, press
ENTER
.
To exit the checking, press or
0......9
.
FLOw
ENTER
46.25 L/S
00.00 L/S
0......9
Fig. 69: Diagram of the "FLOW" parameter of the Test menu
If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press
ENTER
to save the
settings and go back to the Process level.
English