Manual

12
Version of elec-
tronic module SE30
Supply voltage
Output
Order code
Hall 12-36 V DC 2 transistors,
NPN and
PNP
423913
Hall Low
Power
energized via the
Bürkert transmitter
the flow sensor is
connected to
1 NPN
transistor
423914
Ordering codes of fitting S030 can be found within the
related data sheet: refer to the data sheet to select the
fitting appropriate to the process.
English
13
6. TECHNICAL DATA
Conditions of use
Ambient temperature
(operating)
-15 °C to +60 °C
Air humidity < 80%, non condensated
Protection rating IP65, female connector wired,
plugged and tightened
Conformity to standards and
directives
The device conforms to the EC directives through the
following standards:
EMC: EN 61000-6-2, EN 61000-6-3
Pressure: The S030 fitting complies with article 3 of §3
from 97/23/CE directive.
Acc. to pressure directive 97/23/CE, the fitting can only
be used in the following cases (depending on the max.
pressure, the DN of the pipe and the fluid):
Type of fluid Conditions
Fluid group 1 § 1.3.a only DN25
Fluid group 2 § 1.3.a DN 32
or DN > 32 and PNxDN 1000
Fluid group 1 § 1.3.b PNxDN 2000
English
13
14
Type of fluid Conditions
Fluid group 2 § 1.3.b DN200
General data
Pipe diameter DN6 to DN65
The appropriate diameter is deter-
mined using the flow rate / DN / fluid
velocity graphs.
Pressure class Depends on the material of the fitting
used and on the fluid temperature:
refer to the operating instructions of
the fitting used.
Fluid temperature
with fitting S030 in
metal or PVDF
with fitting S030
in PP
with fitting S030 in
PVC
The fluid temperature may be restricted
by the fluid pressure: refer to the ope-
rating instructions of the fitting used.
-15 to +100 °C
0 to +80 °C
0 to +50 °C
Type and data of the
fluid
refer to the operating instructions of
the fitting used.
English
15
Flow rate measuring
range
0,3 to 10 m/s
Accuracy, with standard
K factor
≤ ±(0.5 % of the full scale + 2.5 % of
the measured value)*
Linearity ± 0,5 % of the full scale (10 m/s)*
Repeatability ± 0,4 % of the measured value*
* Determined in the following reference conditions: medium =
water, water and ambient temperatures 20 °C, min. upstream and
downstream distances respected, appropriate pipe dimensions
English
15