User Manual

8.6.3. Entering or determining the K factor of the fitting used
The device determines the flow rate in the pipe using the fitting K factor.
The K factor of the fitting used can either be entered (see Fig. 18) or determined using a teach-in procedure (See Fig. 19).
ENTER
tEACh NO K=000.0
K=48.30FiltER
ENTER
ENTER
0......9
The display shows the last K factor of the fitting, may it have been
entered or determined by a teach-in procedure.
Edit the parameter.
Enter the K factor (value between 0,0001 and 9999,9) of the
fitting used.
Confirm the displayed value.
K-FACtOR
Fig. 18: Entering the K factor of the fitting used
21
Operating and commissioning
Type 8025/8035 battery powered
English