Technical data
Type 8045
6.5. Electrical data
Power supply 18-36 V DC, filtered and
regulated
oscillation rate: ±5 %
Current consumption 300 mA max. (at 18 V DC)
Transistor output DO1
type
function
frequency
Electrical data
duty cycle if f > 2 Hz
min. pulse duration if
f < 2 Hz
protections
NPN / PNP (wiring dependent),
open collector
pulse output (by default), user
configurable
0-250 Hz
5-36 V DC, 100 mA max.
1/2
250 ms
galvanically isolated, and
protected against over-
voltages, polarity reversals and
short-circuits
Relay outputs (DO2 and
DO3)
operating
electrical data of the load
max. breaking capacity
life span
hysteresis (by default), configu-
rable, normally open
250 V AC / 3 A or 30 V DC /
3 A (resistive load)
750 VA (resistive load)
min. 100000 cycles
Current output AO1
specification
max. loop impedance
4-20 mA, sink or source (wiring
dependent), 22 mA to indicate
a fault
1300 W at 36 V DC, 1000 W at
30 V DC, 700 W at 24 V DC,
450 W at 18 V DC
Digital input (DI1)
supply voltage
input impedance
min. pulse duration
protections
18-36 V DC
15 kW
200 ms
galvanically isolated, and pro-
tected against polarity reversals
and voltage spikes