Operating and functions
8.6.8. Configuring the transistor output DO1 to switch a load
depending on two threshold values
OUtPUt DO1 hYstEREs.
DO2
1-= 0.000
1+= 0.000
→ Enter a flow rate value
1)
, associated to the high
threshold, in the unit chosen in the "UNIT" parameter.
→ Confirm.
wiNDOw
→ Enter a flow rate value
1)
, associated to the low
threshold, in the unit chosen in the "UNIT" parameter.
→ Confirm.
iNV YEs
iNV NO
0......9
→ Choose the operating, inverted or not inverted, of the
transistor output.
DEL. 1= 00
→ Enter the time delay before switching value (value
between 0 and 99 s).
→ Confirm.
REtURN
On a version WITH relay out-
puts
On a version WITHOUT relay
outputs
1)
If hysteresis operating: value set for 1- ≤ value set for 1+. If window switching: value set for 1- < value set for
1+.
Fig. 35: Configuration of the DO1 transistor output with switching thresholds