User Manual

8644/Rockwell - 41
SYSTEM DESCRIPTION
Basic electronic module ME02 / 2-fold monostable
Construction
An electric base module consists of a distribution module (backplane bus) and a function module.
The two modules are connected by a 14-pin board-to-board plug.
Possible combinations with valve types
Connection configuration of valve connector
123
Function display of LEDs
reed / green LED
yellow LED
Display of the switching position
no function
Display of network status (only 2nd valve position)
Display of module status (only 1st valve position)
As with the electronic module of the point I/O system, the function module can be installed and
removed during operation. In order to ensure the switching operation, the valve receives a 24 V supply
briefly during installation. The power at the valve is reduced to a quarter after 120 ms.
1Valve +
2 not connected
3Valve -
Basic module type Add-on dimension Valve positions Valve type Function
ME02 2-fold
monostable
11 mm 2
6524 3/2-way
6525 5/2-way
Technical data ME02 / 2-fold monostable
Dimensions W x H x D 22 x 70.5 x 52 mm
Weight 38 g
Storage temperature -20 ... +60 °C
Rated voltage under load DC 24 V
Number of valve outputs 2
Current consumption per valve position during switching 43 mA
Current consumption per valve position after ca. 120 ms 28 mA
Current consumption from the back-wall bus max. 75 mA
Display of valve status 1 yellow LED per valve position
Display of module status
1 red / green LED per modul
(1st valve position)
Display of network status
1 red / green LED per modul
(2nd valve position)
Power dissipation of module in moment of switching 2 W
Power dissipation of module 120 ms after switching procedure
(2 x 0.25 W power loss at resistors, 2 x 0.25 W at valve coils)