XI. Service and Maintenance
NOTICE
Warranty does not cover boiler damage or
malfunction if the following steps are not
performed at the intervals specied.
A. Continuously:
1. Keep the area around the boiler free from combustible
materials, gasoline and other ammable vapors and
liquids.
2. Keep the area around the combustion air inlet terminal
free from contaminates.
3. Keep the boiler room ventilation openings open and
unobstructed.
B. Monthly Inspections:
1. Inspect the vent piping and outside air intake piping
to verify they are open, unobstructed and free from
leakage or deterioration. Call the service technician
to make repairs if needed.
2. Inspect the condensate drain system to verify it is leak
tight, open and unobstructed. Call the service technician
if the condensate drain system requires maintenance.
3. Inspect the ue temperature sensor cap to verify that it
is free from leakage and deterioration. Call the Service
Technician to make repairs, if needed.
4. Inspect the water and gas lines to verify they are free
from leaks. Call the service technician to make repairs
if required.
CAUTION
Water leaks can cause severe corrosion damage
to the boiler or other system components.
Immediately repair any leaks found.
C. Annual Inspections and Service: In addition to the
inspections listed above the following should be performed
by a service technician once every year.
1. If equipped, test the low water cutoff by pressing the
“Test” button located at its end. The yellow light should
come on and “Limit Open” will ash in the Active
Faults screen on the display. Push the reset button
to restore normal operation. If yellow light does not
come on, determine why the low water cutoff is not
working properly.
2. Follow the procedure for turning the boiler off per
Figure 51 “Lighting Instructions”.
3. Inspect the wiring to verify the conductors are in good
condition and attached securely.
DANGER
This boiler uses ammable gas, high voltage electricity, moving parts, and very hot water under high
pressure. Assure that all gas and electric power supplies are off and that the water temperature is cool
before attempting any disassembly or service.
Do not attempt any service work if gas is present in the air in the vicinity of the boiler. Never modify,
remove or tamper with any control device.
WARNING
This boiler must only be serviced and repaired by skilled and experienced service technicians.
If any controls are replaced, they must be replaced with identical models.
Read, understand and follow all the instructions and warnings contained in all the sections of this
manual.
If any electrical wires are disconnected during service, clearly label the wires and assure that the wires
are reconnected properly.
Never jump out or bypass any safety or operating control or component of this boiler.
Read, understand and follow all the instructions and warnings contained in ALL of the component
instruction manuals.
Assure that all safety and operating controls and components are operating properly before placing
the boiler back in service.
Annually inspect all vent gaskets and replace any exhibiting damage or deterioration.