Alpine Installation, Operating, and Service Instructions

56 103448-02 - 6/13
Table 18: Fitting and Valve Equivalent Length
Copper Fitting and Sweat Valve
Equivalent Length (Ft)
Fitting or Valve
Description
Copper Pipe or Valve Size
1 2
90° Elbow 2.5 3.0 4.0 5.5
45° Elbow 1.0 1.2 1.5 2.0
Tee (thru ow) 0.5 0.6 0.8 1.0
Tee (Branch ow) 4.5 5.5 7.0 9.0
Diverter Tee (typical) 23.5 25.0 23.0 23.0
Gate Valve 0.3 0.4 0.5 0.7
Globe Valve 25.0 36.0 46.0 56.0
Angle Valve 5.3 7.8 9.4 12.5
Ball Valve (standard port) 4.3 7.0 6.6 14.0
Ball Valve (full port) 1.9 1.4 2.2 1.3
Swing Check Valve 4.5 5.5 6.5 9.0
Flow-Check Valve
(typical)
54.0 74.0 57.0 177.0
Buttery Valve 2.7 2.0 2.7 4.5
Threaded Fitting and Valve Equivalent Length (Ft)
Fitting or Valve
Description
Black Threaded Pipe or
Valve Size
1 2
90° Elbow 2.6 3.5 4.0 5.2
Long Radius
Elbow (45° or 90°)
1.4 1.8 2.2 2.8
Tee (thru ow) 1.8 2.3 2.7 3.5
Tee (Branch ow) 5.3 6.9 8.1 10.0
Close Return Bend 4.4 5.8 6.7 8.6
Gate Valve (full open) 0.7 0.9 1.1 1.4
Globe Valve (full open) 30.0 39.0 46.0 59.0
Angle Valve (full open) 13.0 17.0 20.0 26.0
Swing Check Valve
(full open)
8.7 12.0 13.0 17.0
Flow-Check Valve
(typical)
42.0 60.0 63.0 83.0
Table 18: Fitting and Valve Equivalent Length
(cont’d)
NOTICE
The Alpine (ALP) boiler heat exchanger is made from stainless steel tubular coil having relatively narrow
waterways. Once lled with water, it will be subject to the effects of corrosion. Failure to take the following
precautions to minimize corrosion and heat exchanger waterways overheating could result in severe boiler
damage.
Before connecting the boiler, insure the system is free of impurities, grease, sediment, construction
dust, sand, copper dust, ux and any residual boiler water additives. Flush the system thoroughly and
repeatedly, if needed, with clear water mixed with concentrated rinse agent to remove these contaminants
completely.
Iron oxide (red oxide sludge Fe
2
O
3
) is produced during oxygenation. To minimize any oxygen presence
in the system, the system must be air free and leak tight. Do not connect the boiler to radiant tubing
without an oxygen barrier. Using automatic water rell is not recommended, however, if such rell is
employed, a water meter must be added to evaluate the makeup water volume taken after initial ll and
eliminate any water leakage as early as possible.
Maintain the water pressure in the boiler at a minimum of 12 PSI.
The boiler water pH must be within 7.5 < pH < 9.5. If the system contains any aluminum components,
pH must be less than 8.5.
Black oxide sludge (magnetite Fe
3
O
4
) forms as the result of continuous electrolytic corrosion in any
system not protected by an inhibitor.
Scale deposit is made up of lime scale contained in most distributed water and settles over the warmest
surfaces of boiler heat exchanger causing subsequent overheating and eventual failure. Water hardness
must be maintained within 3 to 9 grain/gal range.
Refer to Section XI “Service and Maintenance” for recommended heating system water treatment products
(corrosion/scale inhibitors, cleaners etc) and their suppliers.
NOTE: Table 18 is provided as reference to assist in piping design and species equivalent length of typical piping ttings and
valves.
VI. Water Piping and Trim C. Standard Installation Requirements (continued)