e. Not less than 3 ft (as measured to side of vent
termination) from an inside corner of an L-shaped
structure.
f. Not less than 1 ft from the nearest surface of the
terminal to a roof soft.
g. Not directly above, or, not less than 6 ft horizontally
from an oil tank vent or gas meter.
h. Not less than 2 ft from nearest surface of terminal to
an adjacent building.
B. INSTALLATION OF THE VENT HOOD TERMINAL
1. Inspect Direct Vent Conversion Kit Carton for damage.
DO NOT install if any damage is evident.
2. Direct Vent Conversion Kit Carton includes (see Figures
20, 21 and 22):
Direct Vent Hood Assembly (consists of Vent Hood
Body and Vent Hood Tee) – 1 pc
Backing Plate – 1 pc
Vacuum Relief Valve VRV-4 – 1 pc
Hardware Bag (includes high temperature sealant,
fasteners and inner pipe clamps) – 1 pc
Appliance (Boiler Flue Outlet) Adapter – 1 pc
Appliance Clamp Halves – 2 pcs
Cover Sleeve Assemblies – 2 pcs
Cover Ring Assemblies – 2 pcs
3. Remove vent system components from carton and set
aside.
4. Separate the vent hood tee from the vent hood body and
set aside for later use.
5. After determining the location of the venting system
termination, cut the square hole in the wall sized according
to “L” dimension in Table 5, see Figure 19.
6. Wood or vinyl siding should be cut, so that vent hood base
plate mounts directly on the wallboard to provide stable
support. If siding thickness exceeds ½”, use a spacer bar
or board behind the vent hood mounting (base) plate. See
Figure 20.
a. Seal the backside of the vent hood base plate around
the outer pipe of the vent hood with a bead of high-
temperature silicone sealant (provided in Bagged
Hardware).
b. Mount the vent hood body from outside, through the
wall, keeping the outer pipe centered in the hole.
c. Fasten the vent hood body to the outside wall with
appropriate fasteners (installer provided).
d. Seal the edges of the vent hood base plate to the wall
with a high-temperature silicone sealant (provided in
Bagged Hardware).
e. While inside, position the backing plate over the
outer pipe and fasten to inside wall with appropriate
fasteners (installer provided).
Figure 19: Wall Cutout Dimensions
Boiler Model No.
Direct Vent Conversion
Kit Part No.
"L" Dimension
(Inch)
MPO-IQ147
MPO-IQ189
102130-02
MPO-IQ231 1021300-03
TABLE 5: WALL CUTOUT DIMENSIONS
Figure 20: Vent Hood Body Installation
VI. DIRECT VENTING / AIR INTAKE PIPING (continued)