Specifications

19
9) PitchofHorizontalPiping-Pitchallhorizontalpipingsothatanycondensatewhichformsinthepipingwillruntowards
theboiler:
• PitchU.S.Boilerhorizontalconcentricventing5/8”perfoot
• PitchStainlesssteelventing1/4”perfoot.
10)SupportingPipe-Verticalandhorizontalsectionsofpipemustbeproperlysupported:
• SupportU.S.Boilerconcentricventingnearthefemaleendofeachstraightsectionofpipe.
Exception:Verticalrunsofconcentricpipeinanunusedchimney(Figure7.36)needonlybesupportedattheterminal
andatthebaseoftherun.
• Supportstainlesssteelventingascalledforbytheventmanufacturersinstructions.
Figure 7.7: Snorkel Terminal Conguration