Specifications
3
I Product Description
TheFCM070,FCM090andFCM120arealuminumgasredcondensingboilersdesignedforuseinforcedhotwater
heatingsystemsrequiringsupplywatertemperaturesof180°Forless.Theseboilersaredesignedforinstallationona
wall,howevertheymaybeoormountedusinganoptionalpedestalkitavailablefromU.S.BoilerCompany,Inc.This
boilermaybeventedverticallyorhorizontallywithcombustionairsuppliedfromoutdoors.Thisboilerisnotdesigned
foruseingravityhotwatersystemsorsystemscontainingsignicantamountsofdissolvedoxygen.
II Specifi cations
MODEL*
NO.OF
SECTIONS
MAXIMUM
INPUT
(BTU/hr)
MINIMUM
INPUT
(BTU/hr)
D.O.E.
HEATING
CAPACITY
(BTU/hr)
IBRNET
RATING
(BTU/hr)
AFUE(%)
WATER
VOLUME
(Gal.)
APPROX.
NET
WEIGHT
(lb)
FCM070 monoblock 70,000 30,000 63,000 55,000 95.4 0.41 102
FCM090 monoblock 90,000 30,000 80,000 70,000 94.5 0.41 102
FCM120 monoblock 120,000 40,000 107,000 93,000 95.2 0.62 110
*Addsufx“N”fornaturalgasand“P”forpropane.Ratingsarethesameforbothfuels.
Using60/100mmConcentricVentSystemSuppliedwiththeBoiler................................................................25in.
UsingOptional60/100mmConcentricVentComponents:
FCM070
.......................................................................................
32ft
FCM090
.......................................................................................
32ft
FCM120
.......................................................................................
18ft
UsingApproved3”AL29-4CHorizontalStainlessVentSystemandOptionalStainlessSteelVentKit..........55ft
SeeVentingSectionforadditionalventingoptionsandrequirements
TABLE 2.3: MAXIMUM VENT LENGTHS
TABLE 2.2: SPECIFICATIONS
Figure 2.1: General Con guration