XIII. Service and Maintenance
IMPORTANT
WARRANTY DOES NOT COVER BOILER DAMAGE OR MALFUNCTION IF THE
FOLLOWING STEPS ARE NOT PERFORMED AT THE INTERVALS SPECIFIED
1) Continuously:
a. Keeptheareaaroundtheboilerfreefromcombustiblematerials,gasolineandotherammablevaporsandliquids.
b. Keeptheareaaroundthecombustionairinletterminalfreefromcontaminates.
c. Keeptheboilerroomventilationopeningsopenandunobstructed.
2) Monthly
Inspections:
a. Inspecttheventpipingandoutsideairintakepipingtoverifytheyareopen,unobstructedandfreefromleakageor
deterioration.Calltheservicetechniciantomakerepairsifneeded.
b. Inspectthecondensatedrainsystemtoverifyitisleaktight,openandunobstructed.Calltheservicetechnicianifthe
condensatedrainsystemrequiresmaintenance.
c. Inspectthewaterandgaslinestoverifytheyarefreefromleaks.Calltheservicetechniciantomakerepairsif
required.
4) AnnualInspectionsandService:Inadditiontotheinspectionslistedabovethefollowingshouldbeperformedbya
servicetechnicianonceeveryyear.
a. Testthelowwatercutoffbypressingthe“Test”buttonlocatedatitsend.Theyellowlightshouldcomeonand
“E12”shouldashonthedisplay.Pushtheresetbuttononthedisplaytorestorenormaloperation.Iftheyellow
lightdoesnotcomeon,determinewhythelowwatercutoffisnotworkingproperly.
b. FollowtheprocedureforturningtheboilerofffoundintheFCMSeriesLightingandOperatingInstructions.
c. Inspectthewiringtoverifytheconductorsareingoodconditionandattachedsecurely.
CAUTION
WATER LEAKS CAN CAUSE SEVERE CORROSION DAMAGE TO THE BOILER
OR OTHER SYSTEM COMPONENTS. IMMEDIATELY REPAIR ANY LEAKS
FOUND.
CAUTION
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.