Datasheet

11-20-02
SB02450
CC-TRON
®
FNQ-R
Time-Delay Fuses
⁄‹Ω£™∑ ≈ 1⁄Ω™∑, 600 Volt, ⁄Ω¢ to 30 Amps
Form No. FNQ-R
Page 1 of 2
Data Sheet: 1014
Bussmann
®
1.5"
(50.031)
(38.1mm)
.41"
(50.005)
(10.3mm)
Dimensional Data
General Information:
The Bussmann CC-TRON
®
(FNQ-R) was designed to meet
the needs of control circuit transformer protection.
Current-limitation protects down stream components
against damaging thermal and magnetic effects of short-
circuit currents.
High inrush time-delay. Control circuit transformers can
experience inrush currents up to 85 times their full-load
current rating. FNQ-R fuses can be sized according to
NEC and UL requirements and still allow the high inrush
currents, with significantly more time-delay than the UL
minimum value of 12 seconds at 200% for Class CC fuses.
Melamine tube. Nickel-plated brass endcaps.
Carton Quantity and Weight
Ampere Carton
Weight*
Ratings Qty. Lbs. Kg.
⁄Ω¢-30 10 .200 .091
*Weight per carton
Electrical Ratings (Catalog Symbol and Amperes)
FNQ-R-⁄Ω¢ FNQ-R-1‹Ω¡º FNQ-R-3¤Ω¡º FNQ-R-8
FNQ-R-‹Ω¡º FNQ-R-1›Ω¡º FNQ-R-3⁄Ω™ FNQ-R-9
FNQ-R-›Ω¡º FNQ-R-1⁄Ω™ FNQ-R-4 FNQ-R-10
FNQ-R-⁄Ω™ FNQ-R-1flΩ¡º FNQ-R-4⁄Ω™ FNQ-R-12
FNQ-R-flΩ¡º FNQ-R-1°Ω¡º FNQ-R-5 FNQ-R-15
FNQ-R-‹Ω¢ FNQ-R-2 FNQ-R-5flΩ¡º FNQ-R-17⁄Ω™
FNQ-R-°Ω¡º FNQ-R-2⁄Ω¢ FNQ-R-6 FNQ-R-20
FNQ-R-1 FNQ-R-2⁄Ω™ FNQ-R-6⁄Ω¢ FNQ-R-25
FNQ-R-1⁄Ω• FNQ-R-2°Ω¡º FNQ-R-7 FNQ-R-30
FNQ-R-1⁄Ω¢ FNQ-R-3 FNQ-R-7⁄Ω™
Catalog Symbol: FNQ-R
Time-Delay
Application:
Circuit Transformer Protection
Ampere Rating: ⁄Ω¢ to 30A
Voltage Rating: 600Vac (or less)
Interrupting Rating: 200,000A RMS Sym. (UL)
Agency Information:
UL Listed, Std. 248-4, Class CC, Guide JDDZ, File E4273
CSA Certified, Class CC CSA, Class 1422-01,
File 53787–HRC-MISC
†12-30A is 300Vdc and 10k AIR.
Maximum Acceptable Rating of Overcurrent Device*
Maximum Rating of Overcurrent
Rated Primary Protective Device Expressed As A
Current Percent of Transformer Primary
(Amperes) Current Rating
Less than 2A 500**
2A to less than 9A 167
9A or more 125
*UL 508A Table 42.1.
**300% for other than motor control applications.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.

Summary of content (2 pages)