Datasheet

LOW-PEAK
®
LPJ
Dual-Element Time-Delay Fuses 1-60 Amps
Class J – 600 Volt
Form No. LPJ 1-60
Page 1 of 3
Data Sheet: 1006
Bussmann
®
10-2-02
SB02295
2.38"
(± 0.03)
.63"
35A to 60A
1.06"
(± 0.03)
.5"
1A to 30A
.81"
(± 0.03)
2.25"
(± 0.03)
Catalog Symbol: LPJ-_SP
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: 1 to 60A
Voltage Rating: 600Vac (or less)
300Vdc (or less)
Interrupting Rating: 300,000A RMS Sym. (UL)
100,000A dc
Agency Information:
UL Listed — Special Purpose*, Guide JFHR, File E56412
CSA Certified, 200,000 AIR, Class J per CSA 22.2 No. 248.8
Class 1422-02, File 53787
*Meets all performance requirements of UL Standard 248-8 for Class J fuses.
Catalog Symbol and Ampere Ratings
LPJ-1SP LPJ-3SP LPJ-7SP LPJ-25SP
LPJ-1⁄Ω¢SP LPJ-3-¤Ω¡ºSP LPJ-8SP LPJ-30SP
LPJ-1-flΩ¡ºSP LPJ-3⁄Ω™SP LPJ-9SP LPJ-35SP
LPJ-1-°Ω¡ºSP LPJ-4SP LPJ-10SP LPJ-40SP
LPJ-2SP LPJ-4⁄Ω™SP LPJ-12SP LPJ-45SP
LPJ-2⁄Ω¢SP LPJ-5SP LPJ-15SP LPJ-50SP
LPJ-2⁄Ω™SP LPJ-5flΩ¡ºSP LPJ-17⁄Ω™SP LPJ-60SP
LPJ-2°Ω¡ºSP LPJ-6SP LPJ-20SP
Carton Quantity and Weight
Ampere Carton
Weight**
Ratings Qty. Lbs. Kg.
1–30 10 1.09 0.494
35–60 10 1.78 0.808
**Weight per carton.
General Information:
True dual-element fuses with a minimum 10 second time-
delay at 500% overload.
Long time-delay minimizes needless fuse openings due to
temporary overloads and transient surges.
Can often be sized for back-up protection against motor
burnout from overload or single-phasing if other overload
protective devices fail.
High interrupting rating to safely interrupt overcurrents up to
300,000A.
High degree of current limitation due to the fast speed-of-
response to short-circuits.
Faster response to damaging short-circuit currents than
mechanical overcurrent protective devices.
Reduces let-through thermal and magnetic forces in order
to protect low withstand rated components.
Proper sizing provides “no damage” Type “2” coordinated
protection for NEMA and IEC motor control in accordance
with IEC Standard 947-4-1.
Dual-element fuses have lower resistance than ordinary fuses
so they run cooler.
Lower watts loss reduces power consumption.
Unique dimensions assure that another class of fuse with
a lesser voltage rating, interrupting rating or current-Iimiting
ability cannot be substituted.
Space-saving package for equipment down sizing.
Dimensional Data
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Recommended fuseblocks/fuseholders for
Class J 600V fuses
See Data Sheets listed below
• Finger-safe fuseholders - 1152
• Open fuseblocks - 1114
• Open pyramid fuseblocks - 1108

Summary of content (3 pages)