User`s guide

2-1
CHAPTER 2
INSTALLATION
REQUIREMENTS/SPECIFICATIONS
This chapter describes network guidelines, power requirements, and
operating specifications for the MRXI. Be sure that you read this chapter
before you install the MRXI. Your network must meet the requirements
and conditions specified in this chapter to obtain satisfactory performance
from this equipment. Failure to follow these guidelines could result in
poor network performance.
2.1 NETWORK REQUIREMENTS
When connecting a network segment to the MRXI, via a transceiver and
an AUI cable, the following network requirements must be met:
The transceivers used to connect the MRXI meet Ethernet Version 2 or
IEEE 802.3 standards.
The AUI cables connecting the MRXI to the transceivers on the
network match the transceiver type on the network segment, Ethernet
Version 1, Version 2, or IEEE 802.3 type cables, and do not exceed 50
meters in length.
2.2 SELECTING A LOCATION FOR THE MRXI
You can mount the MRXI on a wall, a 19-inch rack, or place it on any
horizontal surface. If you choose not to install the MRXI in a 19-inch
rack, the location must be within reach of the network cabling and meet
the requirements listed below:
An unrestricted free surface area at least 21 inches wide, 18 inches
deep, and 6 inches high is needed.
A single phase 120 Vac, 15A, grounded power receptacle must be
located within 7 feet of the location.
If you use a shelving unit, it must be able to support 30 pounds of static
weight.
The temperature for the selected location must be maintained between
5
°
and 50
°
C, and fluxuate less than 10
°
C per hour.