User Guide

Table Of Contents
PMP 450 Planning Guide
General protection requirements
To adequately protect a PMP 450 installation, both ground bonding and transient voltage surge suppression
are required.
Basic requirements
The following basic protection requirements must be implemented:
The equipment must be in ‘Zone B’ (see Lightning protection zones on page 1-109).
The AP must be grounded to the supporting structure.
A surge suppression unit (600SS) must be installed close to the SM.
The distance between the SM and 600SS should be kept to a minimum.
The drop cable length between the SM and 600SS must be less than 600 mm.
An surge suppression unit (200SS) must be installed within 600 mm (24 in) of the point at which the power
cable enters the building or equipment room.
The drop cable must be grounded at the building entry point.
The drop cable must not be laid alongside a lightning air terminal.
All grounding cables must be a minimum size of 10 mm
2
csa (8AWG), preferably 16 mm
2
csa (6AWG), or
25 mm
2
csa (4AWG).
Grounding cable requirements
When routing, fastening and connecting grounding cables, the following requirements must be implemented:
Grounding conductors must be run as short, straight, and smoothly as possible, with the fewest possible
number of bends and curves.
Grounding cables must not be installed with drip loops.
All bends must have a minimum radius of 203 mm (8 in) and a minimum angle of 90° (Figure 23). A
diagonal run is preferable to a bend, even though it does not follow the contour or run parallel to the
supporting structure.
All bends, curves and connections must be routed towards the grounding electrode system, ground rod, or
ground bar.
Grounding conductors must be securely fastened.
Braided grounding conductors must not be used.
Approved bonding techniques must be used for the connection of dissimilar metals.
Figure 23 Grounding cable minimum bend radius and angle
Error! No topic specified.
1-110
pmp-0047 (March 2014)