This mode is designed for hydronic heating.
Once a heat demand is present, the BTC 1 turns
on the appliance pump and modulates the boiler
to maintain the calculated outdoor reset target at
the boiler inlet sensor. Outdoor reset calculates
the boiler target temperature based on the
outdoor air temperature and reset ratio.
A heat demand is generated when a voltage
between 24VAC and 120VAC is applied across
CD (common demand) and Ht D (heat demand).
Once voltage is applied, the BTC 1 turns on the
Dem 1 segment in the display. If warm weather
shut down (WWSD) is activated, the WWSD
segment is lit.
If WWSD is not activated and the inlet sensor is
½ (half) of the differential below the calculated
BOIL TARGET, the BTC 1 then changes the
modulation output to the START modulation
setting and closes the Stage contacts (pins 15 &
16) to proceed to trial for ignition. The burner
remains at minimum modulation until the flame
is proved and then modulating output changes
the boiler output to maintain the calculated boiler
target temperature at the inlet sensor. If the inlet
sensor reaches ½ (half) of the differential above
the BOIL TARGET, the appliance is shut off.
The boiler pump continues to circulate until the
PUMP DELAY timer expires.
The water temperature is controlled based on a
calculated boiler target temperature. The boiler
start (BOIL START) temperature is pre-set to
70
o
F and the auto re-set limit is set to 210°F and
is fixed. In addition to the auto reset limit the
factory installs a manual re-set limit set to 250°F .
Figure 19: Mode 4 Piping & Electrical Layout
Mode 5: Outdoor Reset using System Sensor
This mode is designed for hydronic heating.
Once a heat demand is present, the BTC 1 turns
on the appliance pump and modulates the boiler
to maintain the calculated outdoor reset target at
the system sensor. Outdoor reset calculates the
boiler target temperature based on the outdoor
air temperature and reset ratio.
A heat demand is generated when a voltage
between 24VAC and 120VAC is applied across
CD (common demand) and Ht D (heat demand).
Once voltage is applied, the BTC 1 turns on the
Dem 1 segment in the display. If warm weather
shut down (WWSD) is activated, the WWSD
segment is lit.
If WWSD is not activated and the system sensor
is ½ (half) of the differential below the calculated
BOIL TARGET, the control then changes the
modulation output to the START modulation
setting and closes the Stage contacts (pins 15
&16) to proceed to trial for ignition. The burner
remains at minimum modulation until the flame
is proved and then the modulating output
changes the boiler output to maintain the
calculated boiler target temperature at the
system sensor. If the system sensor reaches ½
(half) of the differential above the BOIL
TARGET, the appliance is shut off. The
appliance pump continues to circulate until the
PUMP DELAY timer expires. In this case, it is
imperative that the system pump operates
continuously in order to provide constant
circulation past the system sensor.
The water temperature is controlled based on a
calculated boiler target temperature. The boiler
start (BOIL START) temperature is pre-set to
70
o
F and the auto re-set limit is set to 210°F and
is fixed. In addition to the auto reset limit the
factory installs a manual re-set limit set to 250°F .
Figure 20: Mode 5 Piping & Electrical Layout