Service manual

23
9.2 MODE 1 & 2: SETPOINT OPERATION: VIEW DISPLAY
From the Home display;
1) Press [ITEM] to view the following parameters:
Display
Parameter
Name
Parameter Description
Paramet
er
Range
Boiler Target
Temperature
To provide a target setpoint for the
heating system. Setpoint is controlled
to the inlet sensor
---, 35 to 266
o
F
(---, 2 to 130
o
C)
System
Temperature
System Temperature of Primary Loop
NOTE: This parameter is only
available in Mode 2
14 to 266
o
F
(-10
to 130
o
C)
Boiler Outlet
Temperature
Real-time Outlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Inlet
Temperature
Real-time Inlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Delta
T
Real-time temperature difference
between the outlet sensor and the inlet
sensor.
-99 to 252
o
F
(-72 to 140
o
C)
Modulation
Real-time modulating output
percentage
0 to 100%
Total Run
Time Since
Installation
Monitors the amount of operational
time since the MicoFlame was
installed. The first two digits are the
number of thousands of hours and the
three digit display shows the number
of hundreds of hours.
Press simultaneously to reset
the counter
Alternates
between 00 and
999