Service manual

29
Display Parameter Name Parameter Description
Parameter
Range
Warm Weather
Shutdown
Temperature
Warm weather shutdown
temperature using outdoor reset.
35 to 105
o
F,
OFF
(2 to 41
o
C, OFF)
Default = 0:20
min
Temperature Units
Select the desired unit of
measurement
o
F,
o
C
Default =
o
F
9.8 MODE 6 & 7: EXTERNAL TARGET TEMPERATURE INPUT OPERATION: VIEW DISPLAY
From the Home display;
1) Press [ITEM] to view the following parameters:
Display
Parameter
Name
Parameter Description
Parameter
Range
Boiler Target
Temperature
To provide a target setpoint for the
heating system. Setpoint is controlled
to the inlet sensor.
---, 35 to 266
o
F
(---, 2 to 130
o
C)
System
Temperature
Real-time System Temperature
NOTE: This parameter is only
available in Mode 7
14 to 266
o
F
(-10 to 130
o
C)
Boiler Outlet
Temperature
Real-time Outlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Inlet
Temperature
Real-time Inlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Delta
T
Real-time temperature difference
between the outlet sensor and the inlet
sensor.
-99 to 252
o
F
(-72 to 122
o
C)