Service manual

30
Display
Parameter
Name
Parameter Description
Parameter
Range
Modulation
Real-time modulating output
percentage
0 to 100%
Total Run
Time Since
Installation
Monitors the amount of operational
time since the MicoFlame was
installed. The first two digits are the
number of thousands of hours and the
three digit display shows the number
of hundreds of hours.
Press simultaneously to reset
the counter
Alternates
between 00 and
999
9.9 MODE 6 & 7: EXTERNAL TARGET TEMPERATURE INPUT OPERATION: ADJUST DISPLAY
From the Home display;
1) Press simultaneously to view the following parameters:
Display
Parameter
Name
Parameter Description
Parameter
Range
Mode
Operating mode for the boiler.
NOTE: A complete description of
each mode can be found in
section 8.4 Modes of Operation in
this manual.
1 to 8
Default = 1
Differential
Temperature
To provide a modulation rate
above and below the Boiler
Target temperature. For example,
if the value is 10
o
F and the Boiler
Target is 160
o
F the boiler will
begin to modulate at 155
o
F and
shut off at 165
o
F.
Au, 2 to 42
o
F
(Au, -17 to 6
o
C)
Default = Au
Pump Delay
Boiler post pump time after
burner has shut off, in seconds.
OFF, 0:20 to
9:55 min, On
Default = 1:00
min
Temperature
Units
Select the desired unit of
measurement
o
F,
o
C
Default =
o
F