Service manual

42
14 TROUBLE SHOOTING GUIDE
SYMPTOM SOLUTION
1. Power light is not lit when switch is flipped to
“ON”
Check wiring to switch.
Activate push button for latch relay if
provided.
Check circuit breaker.
Check fuse.
2. Water flow light remains off.
Verify that pump is running.
Check wiring to flow switch.
3. Pilot sparks but does not light
Verify that main manual valve is open.
Follow lighting instructions to bleed air out
of pilot line.
Remove main burner and inspect for
moisture or dirt in pilot or in pilot line.
Verify that pilot is sealed to main burner
base.
Verify that gas connections are tight.
4. Pilot lights momentarily, goes out and then
sparks again repeatedly
Observe pilot for proper flame. Adjust if
necessary.
Check pilot flame signal. Properly set pilot
to generate 1.5 µA. D.C. on average.
Remove main burner and ensure that
igniter and ground electrodes are
positioned properly. Clean with steel wool
if necessary.
Verify that back of burner box is fully
engaged into the retaining slot in the
combustion chamber base.
5. Pilot lights but main burner does not fire.
Verify that main manual valve is in “ON”
position.
Check wiring to valve from ignition control.
6. Main burner lights but cycles off after a few
minutes
Verify that high limit is set high enough to
prevent short cycling.
Check pilot flame signal (µA).
Adjust pilot pressure for steady flame
Remove main burner. Check position of
igniter and ground electrode. Clean with
steel wool if necessary.
7. Appliance starts to whine as the temperature
rise increases.
Verify that all air is bled from system.
Verify that the static pressure in cold
system is at least 15 psig at the highest
point in the system.
Check temperature rise across appliance
to ensure adequate water flow.
If necessary, increase static water
pressure and decrease gas pressure.