Programming instructions

54
The Ventilation settings window is where you program curtain settings.
A
D
B
C
Temperature
Idle band (+/
1°F)
When the temperature is within the idle band, the curtain remains in its current
position.
Set point (80°F)
Open run (00:30 mm:ss)
If the temperature rises above the idle band, the curtain opens for the open run duration.
Time (duration)
Open idle (02:00 mm:ss)
After the curtain opens for the open run duration, it holds its position for the open idle
duration.
Close run (01:00 mm:ss)
If the temperature drops below the idle band, the curtain closes for the close run duration.
Close idle (01:00 mm:ss)
After the curtain closes for the close run duration, it holds its position for the close idle
duration.