2. WATER CONNECTIONS
Important: before proceeding, disconnect the humidi er from
the power supply.
Models UE001 to UE018 Models UE025 to UE065
1
1
4
5
3
4
6
5
4
6
7
2
2
3
Fig. 2.a
Water connections:
□
1.
install a manual valve upstream of the installation (to be able
to cut o the water supply);
□
2.
connect the humidi er to the water supply. On models
UE001 to UE0018, use a hose with 3/4’’G ttings (see par.
11.2 “Technical speci cations” , compatible CAREL hose: code
FWH3415000). On models UE025 to UE065 connect the hose
with the non-return valve supplied (code FWHDCV0000) to
prevent the water inside the humidi er from coming into
contact with the mains water;
□
3.
install a mechanical lter to trap any solid impurities (to be
connected downstream of the tap);
□
4
connect a section of non-conductive pipe or hose for draining
(resistant to temperatures of 100 °C (212 °F) and with a
minimum inside diameter of 40 mm/1.6”);
□
5
prepare a funnel to interrupt continuity in the drain line;
□
6
connect a drain trap to prevent the return of bad odours
(minimum inside diameter 40 mm/1.6”);
□
7
in models UE025 to UE0065: connect a drain hose ( minimum
inside diameter 15 mm ( 0.59” )) from the bottom tank of the
humidi er (this can run into the drain funnel).
Important
Important: when installation is completed, ush the supply hose
for around 30 minutes by piping water directly into the drain,
without sending it into the humidi er. This will eliminate any scale or
processing residues that may block the drain pump and cause foam
when boiling.