5. REMOTE TERMINAL AND SUPERVISORY NETWORK
5.1 Remote display terminal
The display terminal can be detached from the humidi er and moved up
to 30 m (98 feet) away.
21 21 3 21
M6
32
M7
12 12
M8
12
M5
21
M3
21
M9
COM
R
Y
G
M12
M10
M11
321
M14
M1 M2
123 1 2 3 4 5 6 7
J1
JS6
UEY
controller
2
1
3
2
drain
esc
Fig. 5.a
Key:
1
telephone cable 6 wires (up to
10 m (33 ft)
(1)
/ 98 feet distance);
2 two EMC  lters (code 0907858AXX) to be applied to the ends of the
telephone cable;
3 remote display terminal.
Note: to  ll the empty space left by the display terminal on the
humidi er, use CAREL kit code HCTREW0000.
(1)
For lengths greater than 10 m (33 ft) use shielded cable with the shield
connected to PE both on the terminal side and the controller side
5.2 RS485 supervisory network (M1.1-M1.3)
M.1.1
M.1.2
M.1.3
+-G0
for models
UEY*000/UEY*100
Rx- / Tx - Rx+ / Tx +
for models UEY*200
Fig. 5.b
Important: for the RS485 connections in household (IEC EN
55014-1) and residential (IEC EN 61000-6-3) environments, use
shielded cable (with shield connected to PE both on the terminal side
and the controller side) with maximum shielded cable length: speci ed
by the EIA RS485 protocol, equivalent to European stan-dard CCITT V11,
using shielded twisted pair cable, AWG26, 485 input stage impedance
1/8 unit-load (with this con guration, a maximum of 256 devices can be
connected) laid in separate conduits from the power cables.