“UE BASIC” +0300042EE - rel. 1.0 - 02.12.2009
6. STARTING AND USER INTERFACE
steam production in progress
cylinder  lling in progress
foam in the cylinder
presence water in the cylinder
cylinder water drain in progress
6.4 Keypad
key function
return to the previous display
from the main screen: pressed for 5 seconds disables/
enables the humidi er
UP from the main screen: display the humidi cation values
(current, conductivity,....), see the following paragraph
from the list of parameters: circular navigation of the
parameters and set the values
DOWN from the main screen: display the humidi cation values
(current, conductivity,....)
from the list of parameters: circular navigation of the
parameters and set the values
ENTER
(PRG)
for 2 seconds: access the list of parameters
from the list of parameters: select and con rm (like the
“Enter key on a computer keyboard)
6.5 Main display
The display on the humidi er normally shows the current steam
production (kg/h, basic display).
To display other values, press UP or DOWN and scroll the following list:
input signal (0-100%, or ON/OFF if A0=0)
access alarm log (HYS ) (**)
set maximum steam production (parameter P0) (*)
current (A)
conductivity (S/cm)
cylinder hour counter (h)
To return to the basic display, press ESC.
Parameter C0 (see chap. 7) can be used to change the value of the basic
display (default: current steam production).
(*) To modify the maximum steam output (P0) press:
ENTER (display:
)
UP or DOWN to set the value percentage of production (from 20 to
100%)
ENTER to con rm the new value
Press ESC to return to the main screen
Parameter P0 can also be accessed from the list of parameters (see chap. 7).
(**) To display the alarm log (HYS
) press:
ENTER (the most recent alarm is shown)
UP or DOWN to scroll the list of alarms in chronological order
press ESC to return to the main screen
To delete the list of alarms press UP and DOWN for 5 seconds (inside the
alarm log), when the list has been reset the display will show ‘res.
6.6 Disabling
The humidi er can be disabled in 3 di erent ways:
Opening contact M2.4 and M2.5 (enable) : the display shows C--
From serial (see Chap. 7 Digital 2) : the display shows S--
From terminal (see ESC button) : the display shows t--
Before starting the humidi er, check:
water connections: chap. 2. In the event of water leaks do not start the
humidi er before having resolved the problem;
steam distribution: chap. 3 and electrical connections chap. 4 .
6.1 Starting
1
1
0
ON
2
if the cylinder is new, run a pre-wash cycle by pressing ENTER +
DOWN for 5 sec. (the cylinder is  lled and emptied three times,
cleaning the inside walls from impurities).
A display shows the symbol PRE Cln
6.2 Stopping
1
empty the water in the cylinder to avoid stagnation (see paragraph 6.12
“Manually drain the water in the cylinder”).
2
1
0
OFF
6.3 Display
humiSteam
basic
esc
μS/cm
Fig. 6.a
Key:
manually drain the cylinder (see paragraph 6.6)
power supply (green LED)
humidi er operating (yellow LED)
Flashing: steam production not yet in steady operation
Steady: steam production in steady operation
alarm (red LED, not  ashing)
Alarm activated: LED  ashing and buzzer active
If an alarm is active pressing ESC mutes the buzzer and the
LED comes on steady, pressing ESC again resets the alarms
(see Chap. 8)
conductivity value
time in seconds
instant current value in Amperes
real hour counter
steam  ow-rate (Imperial system)
steam production as a percentage of rated capacity
steam  ow-rate (international system, default)
parameter programming in progress (parameter setup)
maintenance request (alarm active) or display alarm log (HYS)
on steady: external fan or steam production active.
Flashing: external fan or steam production awaiting start/
stop
3 digits, after 999 the display shows to indicate 1000 (only
three digits plus point - between the  rst and the second
digit- are displayed
).