User manual

18
ENG
“UE BASIC” +0300042EE - rel. 1.0 - 02.12.2009
installatoreutenteassistenza
6.7 Recalling the manufacturer defaults
From the main screen press ENTER until the password screen is shown:
Enter the password 50
The message dEF is displayed,  ashing
Con rm by pressing ENTER or exit by pressing ESC
If no button is pressed for 30 seconds, the display returns to the main
screen.
6.8 Display software release
1) when switching on the unit to display “rel. x.y “(example rel. 1.2)
2) during operation
a) display: from main screen press ESC and UP appear in sequence:
the size dell’umidi catore, the voltage, the number of phases and the
software release
b) via network using integer variable 81. Format = # # #. # “(e.g. 12 =
release 1.2)”.
6.9 Match digit (match between the
softwares of board and terminal)
humiSteam basic veri es the matching between the softwares of the
controller and the terminal at the start-up. The 8th digits for board and
9th for terminal of both codes must be equal.
If there is no match, on power-up after displaying the software release, and
in normal operation when pressing UP+PRG, the red LED will remain on for 5
seconds, and the following error message will be displayed:
“X – Y, where “X” and “Y are the 2 di erent 8th digits. Refer to the after-
sales service.
6.10 Reset cylinder hour counters
Access parameter da’ (see chap. 7)
press UP and DOWN for 5 seconds
When the counter has been reset, the display shows ‘res’ .
6.11Parameters: Saving/recalling the user
settings
From the main screen, a copy of the user settings can be saved at any
time, and then later recalled.
To save the settings::
From the main screen press:
ENTER for 2 seconds,
enter the password 51 using the UP or DOWN button and press ENTER, the
message UbP (Backup User parameters)  ashes
press ENTER: the message -L- is displayed,  ashing
press UP or DOWN, the message–S- (Save) is displayed,  ashing,
press ENTER to save a copy of the user settings, or press ESC to cancel the
operation
NOTE: the copy of the user parameters saved previously will be
overwritten with current user settings.
To recall the settings::
From the main screen press:
ENTER for 2 seconds,
enter the password 51 using the UP or DOWN button and press ENTER,
the message UbP (Backup User parameters)  ashes
press ENTER: the message -L- (Loading) is displayed  ashing,
press ENTER to recall the previously saved copy of the user settings, or
press ESC to cancel the operation.
If no button is pressed for 30 seconds, the display returns to the main
screen, without performing the operation.
6.12 Manually drain the water in the cylinder
Total drain in operation
Press UP and DOWN together for 2 seconds (the message dr on the
display alternating with ‘tot indicates the function has been activated).
Press UP and DOWN again for 2 seconds to stop the drain cycle. The
drain cycle in any case ends automatically.