User manual

20
ENG
“UE BASIC” +0300042EE - rel. 1.0 - 02.12.2009
8. ALARMS
code display and
symbol
var. code
I89
meaning causes solution reset (press) alarm relay
activation
e ect red LED signal
on board (*)
(if terminal
not
connected)
E0 - 1008Hex calibration parameter
software veri cation
errora
internal memory
error
if the problem persists,
contact the CAREL service
center
-- yes humidi cation
stopped
3 fast  ashes
E1 - 1004Hex parameter
con guration error
error in the
parameters user
if the problem persists,
contact the CAREL service
center
-- yes humidi cation
stopped
4 fast  ashes
EH
1010Hex excess current over-current at the
electrodes;
probable electrode
malfunction or
water conductivity
temporarily too high
(especially when
starting after a short
stop)
1. check the operation of
the drain pump
2. check the seal of the
ll electrovalve when not
energised
3. drain part of the water
and re-start
AUTO yes humidi cation
stopped
2 fast  ashes
EP
1020Hex no production excessive reduction
in production , or
cylinder completely
depleted or water
Perform maintenance on
the cylinder
ESC yes humidi cation
stopped
4 slow  ashes
CY
3001Hex cylinder life pre-alarm the cylinder full
limit of 1500 h
(default)
perform maintenance
and/or replace the
cylinder
ESC
(the alarm is
reactivated
after 50 hrs)
no signal only 7 fast  ashes
EF
2004Hex no water Check:
water supply and  ll
valve;
whether the manual
drain is open;
blockage of the  lter on
the  ll solenoid valve;
whether there is
excessive backpressure
in steam outlet,
preventing the  ow of
water into the cylinder
by gravity;
that the steam outlet
hose is not choked
or that there are no
pockets of condensate;
that the power cables
are connected to the
cylinder
automatic
(after 10
minute
waiting time)
yes
(in 10
minute
waiting
time)
humidi cation
stopped for 10
minutes only
3 slow  ashes
Ed
2008Hex failed drain check the drain pump and
drain connection
ESC yes humidi cation
stopped
5 slow  ashes
CP
3004Hex cylinder being
depleted signal
cylinder life ending,
perform maintenance
and/or replace the
cylinder
AUTO no signal only 6 slow  ashes
CL 3008Hex cylinder depleted
signal
cylinder life ended,
perform maintenance
and/or replace the
cylinder
AUTO no signal only 10 slow  ashes
EA
3002Hex foam excessive foam in
the cylinder during
boiling.
the formation of
foam is generally
due to the presence
of surfactants in the
water (lubricants,
solvents, detergents,
water treatment
agents, softeners)
or an excessive
concentration of
dissolved salts.
1. drain the water supply
lines
2. clean the cylinder
3. check for the presence
of softeners
(in this case, use another
type of water
or reduce the softening)
ESC no signal only 9 slow  ashes
E2 3010Hex memory backup fails internal memory
error
if the problem persists,
contact the CAREL service
center
-- no signal only 6 fast  ashes