9.3 Cleaning and maintenance of the cylinder
Replacement
Important: he cylinder must be only be replaced by quali ed
personnel, and with the humidi er unplugged from the power
supply.
In normal conditions, the disposable cylinders should be replaced after
one year (or 2500 hours of operation, if cleaned periodically), while the
openable cylinders last 5 years (or 10,000 hours of operation, if cleaned
periodically). They must be replaced immediately – even before the
speci ed intervals – if any anomalies occur. For example, when the lime
scale inside the cylinder prevents the correct  ow of electric current.
Replacement procedure::
empty all the water (see chap. 6);1.
turn o the humidi er (switch “0”), and open the mains disconnect 2.
switch on the power supply (safety procedure);
wait for the humidi er and the cylinder to cool down;3.
remove the front cover;4.
disconnect the electrical cables from the cylinder;5.
release the cylinder from the locking device and lift it to remove it;6.
insert the new cylinder (make sure that the model and the power 7.
supply of the new cylinder correspond to the rated data);
fasten the cylinder; 8.
reconnect the electrical cables to the cylinder;9.
replace the front cover;10.
switch on the humidi er;11.
reset cylinder operating hour counter (see parameters da chap. 7);12.
Activate the wash new cylinder procedure, pressing ENTER + DOWN 13.
for 5 seconds
Periodical checks
After one hour of operation: check for any signi cant water leaks.
Every 15 days or no more than 300 operating hours: check operation,
the absence of signi cant water leaks, the general conditions of
the casing. Check that during operation there are no arcs or sparks
between the electrodes.
Every 3 months or no more than 1000 operating hours:
disposable cylinders: check operation, the absence of signi cant -
water leaks and if necessary replace the cylinder;
openable cylinders: if there are signi cantly blackened areas, check -
the deposits on the electrodes and clean them, using the speci c
electrode and gasket kit.
Every year or no more than 2500 operating hours:
disposable cylinders: replace; -
openable cylinders: if there are signi cantly blackened areas, check -
the deposits on the electrodes and clean them, using the speci c
electrode and gasket kit.
After 5 years or no more than 10,000 operating hours: replace the
openable cylinder.
After extended operation, or when using water rich in salts, the solid
deposits that naturally form on the electrodes may grow until attaching
to the inside wall of the cylinder. If these deposits are conductive the heat
generated may overheat the plastic until it melts, with the risk of very hot
water being released.
Important: In the event of water leaks, disconnect the power
supply from the humidi er as the water may conduct electricity.
9.4 Mechanically draining the water in the
cylinder
Drain due to gravity without activating the humidi er, recommended if:
humidi er decommissioned;
to empty the cylinder without switching the humidi er on.
Mechanical drain:
make sure that the humidi er is not powered;
remove the cover;
activate the mechanical device under the cylinder (see part A, Fig. 9.e).
Models UE001 to UE018 Models UE025 to UE065
A
A
Fig. 9.e
9.5 Cylinder connection, three-phase models
UE025 to UE065
production
(kg/h)
conductivity (μS/cm) power supply (V)
230 400
25 75/350 µS/cm A B
350/1250 µS/cm B B
35 75/350 µS/cm A B
350/1250 µS/cm A B
45 75/350 µS/cm A A
350/1250 µS/cm A B
65 75/350 µS/cm / A
350/1250 µS/cm / B
Tab. 9.f
The cable ends must be tightened with the top nut to 3 Newton • m.
(units with BL*T5* cylinder only)
1
2
3
1
2
3
A
B
C
F
E
D
A
2
3
3
1
1
2
B
A
B
C
F
E
D
Fig. 9.f
UE001-3-9
single-phase
75...1250 μS
1 = A
2 = D
75...1250 μS
1 = A
2 = C
3 = E
UE003 200 - 230 - 400 - 460 V
three-phase
A
CE
A
D
75...1250 μS
1 = A
2 = C
3 = E
UE005-8 400 - 460 - 575 V
three-phase
CE
A
75...1250 μS
1 = A
2 = C
3 = E
UE0010-18 400 - 460 - 575 V
three-phase
CE
A
UE005 200...230 V
single-phase
175...350 μS
1 = A - E - C
2 = B - F - D
350...1250 μS
1 = A - B - C
2 = D - E - F
A
F
E
B
C
D
UE005-8 / UE010-15
200...230 V three-phase
75...350 μS
1 = A - D
2 = B - E
3 = C - F
350...1250 μS
1 = A - B
2 = C - D
3 = E - F
A
F
E
B
C
D
Three-phase and sigle-phase models UE01 to UE018