11.1 humiSteam Basic models and electrical speci cations
The following table lists the electrical data relating to the power supply
of the various models and the speci cations of each. Note that some
models may be powered at di erent voltages, obviously with di erent
power input and steam production.
power supply rated speci cations
model steam production
(2; 4)
(kg/h)
power
(2)
(kW)
code voltage
(1)
(V - type)
current
(2)
(A)
TAM con guration
(5)
cable
(3)
(mm
2
)
line fuses
(3)
(A /
type)
wiring diagram
(Fig.)
UE001 1.5 1.1 D 230 - 1~ 4.9 11.a 100 1.5 10 A / fast-blow 10.a
UE003 3.0 2.2 D 230 - 1~ 9.8 11.d 300 2.5 16 A / fast-blow 10.a
K 230 - 3~ 5.6 11.a 100 2.5 16 A / fast-blow 10.b
L 400 - 3~ 3.2 11.d 100 1.5 10 A / fast-blow 10.b
UE005 5.0 3.7 D 230 – 1~ 16.3 11.e 300 6.0 32 A / fast-blow 10.a
K 230 - 3~ 9.4 11.c 300 2.5 16 A / fast-blow 10.b
L 400 - 3~ 5.4 11.a 100 1.5 10 A / fast-blow 10.b
UE008 8.0 6.0 K 230 – 3~ 15.1 11.c 300 6.0 32 A / fast-blow 10.b
L 400 – 3~ 8.7 11.a 100 2.5 16 A / fast-blow 10.b
UE009 9.0 6.7 D 230 - 1~ 29.3 11.a 500 10.0 40 A / fast-blow 10.a
UE010 10.0 7.5 K 230 – 3~ 18.8 11.c 300 6.0 32 A / fast-blow 10.b
L 400 – 3~ 10.8 11.d 300 2.5 16 A / fast-blow 10.b
UE015 15.0 11.2 K 230 – 3~ 28.2 11.c 500 10.0 40 A / fast-blow 10.b
L 400 – 3~ 16.2 11.a 300 6.0 32 A / fast-blow 10.b
UE018 18 13.5 L 400 – 3~ 19.5 11.a 300 6.0 32 A / fast-blow 10.b
UE025 25 18.7 K 230 – 3~ 47.1 11.b 500 25 63 A / fast-blow 10.c
L 400 – 3~ 27.1 11.c 500 16 50 A / fast-blow 10.c
UE035 35 26.2 K 230 – 3~ 65.9 11.c 700 35 100A / fast-blow 10.c
L 400 – 3~ 37.9 11.c 500 16 60 A / fast-blow 10.c
UE045 45 33.7 K 230 – 3~ 84.7 11.b 700 50 75 A / fast-blow 10.c
L 400 – 3~ 48.7 11.c 700 25 80 A / fast-blow 10.c
UE065 65 48.7 L 400 – 3~ 70.4 11.c 700 35 100A / fast-blow 10.c
Tab. 11.a
11. GENERAL FEATURES AND MODELS
(1) tolerance allowed on the rated mains voltage: -15%, +10%;
(2) tolerance on the rated values: +5%, -10% (EN 60335-1);
(3) recommended values refer to laying PVC or rubber cables in closed conduits, 20 m
(65.6 feet) long; the standards in force must however be observed,
(4) rated max instant steam production: the average steam production may be
a ected by external factors, such as: ambient temperature, water quality, steam
distribution system;
(5) refer to the wiring diagrams to verify the data are not absolute and if these di er
from local standards, the latter must prevail.
TAM con gurations and connections (transformer for
measuring the current)
Important: the con gurations and connections are already made
by CAREL, and no changes are required. The following diagrams
represent possible connection modes and may be useful in the event of
serious electrical malfunctions on the humidi er.
All operations must only be performed by quali ed personnel, improper
use may cause serious damage.
one cable turn one turn of the two
cables of the same phase
two cable turns of the
same phase
one cable in double
turn mode
three cable turns of the
same phase
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
Fig. 11.a Fig. 11.b Fig.11.c Fig.11.d Fig.11.e
Important: to avoid interference, separate the power cables
from the probe cables.