User manual

39
ENG
“UE BASIC” +0300042EE - rel. 1.0 - 02.12.2009
11.7 CONTROLLING THE BOARD VIA NETWORK
The variables shown in the list are only some of the total variables available.
DO NOT CONFIGURE VA-RIABLES THAT ARE NOT SHOWN IN THE TABLE,
OTHERWISE THE OPERATION OF THE HUMIDIFIER MAY BE AFFECTED. NOTE:
The software release is made up of 4 digits and is shown on the sticker on
the back of the controller. For example, the code “1.080” indicates: hardware
release “1.0” and software release “8.0”. Make sure the correct network address
has been set for parameter C3 (internal variable I13) before setting the
address of the CPY controllers. Each humidi er is con gured by default with
address 1, two units cannot have the same address.
“A”
analogue variables* (Modbus®: REGISTERS)
CAREL - Modbus®
3 param. d9: rated capacity in kg/h (see the table of parameters)
4 param. d7: maximum production in kg/h (see the table of parameters)
15 param. d3: instant steam  ow-rate in kg/h; read-only. Format “#### = #### (100 = 100 kg/h)”.
30 param. d6: current (A); read-only. Format “#### = #### (16 = 16a)”.
33 param. C8: maximum time with no data (sent to controller) over RS485 to generate stop production + “SU” alarm (see parameters table)
* The data from the controller should be interpreted with a decimal point.
E.g.: var. 3=150 means 15.0 kg/h
“I”
integer variables (Modbus®: REGISTERS)
CAREL Modbus®
1 256 param. P0: maximum production (see the table of parameters)
2 257 param. A0: operating mode (see the table of parameters)
3 258 param. A1: unit of measure (see the table of parameters)
4 259 param. A2: type of production request (see the table of parameters)
5 260 param. b1: additional functions (see the table of parameters)
6 261 param. b2: o delay time (see the table of parameters)
7 262 param. b4: water conductivity (see the table of parameters)
8 263 param. b5: conductivity pre-alarm threshold (see the table of parameters)
9 264 param. b6: conductivity alarm threshold (see the table of parameters)
10 265 param. b7: foam control threshold (see the table of parameters)
11 266 param. b8: conductivity control inside the cylinder in steady operation compared to rated value
12 267 param. C0: rated value displayed (see the table of parameters)
13 268 param. C3: serial port address (see the table of parameters)
14 269 param. C4: baud rate (see the table of parameters)
15 270 param. C5: supervisor: frame (see the table of parameters)
16 271 param. C6: serial response transmission delay (see the table of parameters)
17 272 param. b9: reduce duration of drain to dilute cycle (see the table of parameters)
18 273 param. bb: cylinder maintenance limit time in hours (see the table of parameters)
19 274 param. bE: time limit between two periodical drain cycles (see the table of parameters)
20 275 param. bF: days delay for drain due to inactivity (see the table of parameters)
44 299 param. d1: external control signal
see paragraph controlling production using variables I62 and I63, read-only; example format “ #### = #### (0%-100%, step 1%)”
46 301 humidi er status (read-only)0 = not active (no request, shutdown or disabled); 1 = start evaporation cycle; 2 = water  ll in progress; 3 =
evaporation in progress ; 4 = AFS drain ; 5 = water drain (to dilute or manual); 6 = end of water drain; 7 = complete drain for long inactivity; 8 =
complete drain from manual or network control; 9 = no water management; 10 = pre-wash; 11 = periodical drain
47 302 type of humidi cation stage (read-only) 0 = not active; 1 = soft start; 2 = start of steady production the reduced production;
3 = steady production; 4 = reduced production; 5, 6, 7 = soft start
49 304 param. d5: conductivity of supply water [µS/cm] read-only, see the table of parameters
54 309 param. db: unit hour counter (not resettable, see the table of parameters)
55 310 param. dA: cylinder hour counter (resettable, see the table of parameters)
62 317 controls via RS485 ; bit 0: reset alarm log; bit 1: reset counter dA; bit 2: production request via variable I63; bit 3: pre-wash; bit 4: reset active
alarms. ; Bit 6:  ag to enable stop production + alarm for serial disconnected; Bit 7:  ag to request oldest alarm; Bit 8:  ag to request most
recent alarm; Bit 9:  ag to load  rst alarm in log; Bit 12:  ag to enable create user backup. Except for bit2, the others are always read as 0. On
power-up, all the bits are equal to 0.
63 318 production request via network (when I62 bit2 = 4) (0%-100%, step 1%).
64 319 control board match-digit (read-only)
67 577 param. c7 (see the table of parameters)
83 338 alarm status: Bit 0: at least one BLOCK alarm present ; Bit 1:at least one DISAB alarm present; Bit 2: at least one WARN alarm present
84 339 alarms with shutdown (read-only) bit n=0 alarm not active, bit n=1 alarm active. See table of alarms: bit 0: alarm Mn; bit 1: alarm EC; bit 2:
alarm E1; bit 3: alarm E0; bit 4: alarm EH; bit 5: alarm EP; bit 6: not used; bit 7: not used.
85 340 alarms with disabling (read-only) bit n=0 alarm not active, bit n=1 alarm active. See table of alarms: bit 0: alarm EU (automatic reset); bit 1:
alarm E3; bit 2: alarm EF (automatic reset); bit 3: alarm Ed; bit 4: not used; bit 5: not used; bit 6: not used; bit 7: not used.
86 341 warnings (read-only) bit n=0 alarm not active, bit n=1 alarm active. See table of alarms: bit 0: pre-alarm CY; bit1: warning Ec; bit 2: pre-alarm
EA; bit 3: pre-alarm CP; bit 4: pre-alarm CL; bit 5, bit 6, bit 7: not used
89 344 read line in alarm log (see variable I62, bit7-8-9 )
Tab. 11.g