Datasheet

Specication are subject to change without notice EM111 DS 291015
1
Energy Management
Energy Analyzer
Type EM111
Product description
Single-phase energy
analyzer with backlit LCD
display with integrated touch
keypad. Particularly indicated
for active energy metering
and for cost allocation in
applications up to 45 A (direct
connection), with dual tariff
management availability.
It can measure imported
and exported energy or be
programmed to consider only
• Single phase energy analyzer
• Class 1 (kWh) according to EN62053-21
• Class B (kWh) according to EN50470-3
• Accuracy ±0.5% RDG (current/voltage)
• Direct current measurement up to 45AAC
• Backlit LCD display with integrated touch key-pad
• Energy readout on display: 7 digit
• Variable readout on display: 4 digit
• Energy measurement: kWh and kvarh (imported/
exported); kWh+ by 2 tariffs
• System variables, kW, kvar, V, A, PF, Hz, kWdmd,
kWdmd peak
• Self power supply
• Dimensions: 1-DIN module
• Protection degree (front): IP51
• Pulse output (optional, by open collector PNP)
• RS485 Modbus port (optional)
• M-bus port (optional)
• Digital input (for tariff management)
• Easy connection or wrong current direction detection
Certied according to MID Directive (option PF only):
see “how to order” below
the imported one. Housing for
DIN-rail mounting, with IP51
front degree protection. The
meter is optionally provided
with pulse output proportional
to the active energy being
measured, RS485 Modbus
port or M-bus port.
How to order
EM111-DIN AV8 1 X O1 PF B
Certied according to MID Directive, Annex “B”
+ Annex “D” or Annex “B” + Annex “F” for legal
metrology relevant to active electrical energy meters
(see Annex MI-003 of MID). Can be used for scal
(legal) metrology.
MID
Type Selection
Model
Range code
System
Power supply
Output
Option
Measurement
Range code
AV8: 230VLN AC - 5(45)A
(Direct connection)
AV7: 120VLN AC - 5(45)A
(Direct connection)
Power supply
X: Self power supply
-30% +20% of the
rated measuring input
voltage, 45 to 65Hz
Output
O1: pulse output
S1: RS485 Modbus port
M1: M-bus port
System
1: 1-phase 2-wire
Option
PF: Certied according to MID Directive, Annex”B” +
Annex “D” for legal metrology relevant to active
electrical energy meters (see Annex MI-003 of MID).
Can be used for scal(legal) metrology.
Measurement
B: Only the total positive energy meter is certied
according to MID. Negative energy is not measured.

Summary of content (10 pages)