Datasheet

EM111
Specication are subject to change without notice EM111 DS 291015
5
General specifications
Operating temperature -25 to +65 °C, indoor,
(R.H. from 0 to 90% non-
condensing @ 40°C)
Storage temperature -30°C to +80°C (R.H. <
90% noncondensing @
40°C)
Overvoltage category Cat. III
Insulation (for 1 minute) 4000 VAC RMS between
measuring inputs and
digital/serial output (see
table) 4000 VAC RMS
Dielectric strength 4000 VAC RMS for 1
minute
EMC According to EN62052-11
Electrostatic discharges 15kV air discharge;
Immunity to irradiated
electromagnetic elds Test with current: 10V/m
from 80 to 2000MHz;
Test without any current:
30V/m from 80 to
2000MHz;
Burst On current and voltage
measuring inputs circuit:
4kV
Immunity to conducted
disturbances 10V/m from 150KHz to
80MHz
Surge On current and voltage
measuring inputs circuit:
4kV;
Radio frequency According to CISPR 22
Standard compliance
Safety EN62052-11
Metrology EN62053-21, EN50470-3
Approvals CE, MID (PF option only)
Connections
Cable cross-section area Measuring inputs: max. 6
mm
2
with/without metallic
cable ferrule; Max. screw
tightening torque: 1.1 Nm
Other terminals 1.5 mm², Min./Max. screws
tightening torque: 0.4 Nm
Housing
Dimensions (WxDxH) 17,5 x 63 x 91,5 mm
Material Noryl, self-extinguishing:
UL 94 V-0
Sealing covers Included
Mounting DIN-rail
Protection degree
Front IP51
Screw terminals (cable inputs) IP20
Weight Approx. 80 g (packing
included)
Power supply specifications
Self power supply
AV8 230VAC VL-N, -30% +20%
50/60Hz
AV7 120VAC VL-N, -30% +30%
50/60Hz
Power consumption ≤ 1.0W, ≤ 8VA