User Manual

Energy management
EM24-DIN PFA, PFB & X models - Communication Protocol
12
2.9.9 User configuration menu
MODBUS: read and write mode Table 2.9-9
Modicom
address
Physical
address
Length
(words)
VARIABLE
ENG. UNIT
Data
Format
Notes
304365
110Ch 1 ID code of user 1 UINT 16
304366
110Dh 1 ID code of user 2 UINT 16
304367
110Eh 1 ID code of user 3 UINT 16
Value min = 1
Value max = 9999
2.9.10 Digital input configuration menu
MODBUS: read and write mode Table 2.9-10
Modicom
address
Physical
address
Length
(words)
VARIABLE
ENG. UNIT
Data
Format
Notes
304386
1121h 1 Digital input 1 type
UINT 16 Value=0: Sync mode
Value=1: Tariff mode
Value=2: Gas counter
Value=3: H2O cold counter
Value=4: H2O hot counter
Value=5: H2O hot KWh counter
Value=6: External counter
Value=7: REM (remote function)
All other values are considered as
value=0
304387
1122h 1 Digital input 2 type
UINT 16 Value=0: Sync mode
Value=1: Tariff mode
Value=2: Gas counter
Value=3: H2O cold counter
Value=4: H2O hot counter
Value=5: H2O hot KWh counter
Value=6: External counter
Value=7: REM (remote function)
All other values are considered as
value=0
304388
1123h 1 Digital input 3 type
UINT 16 Value=0: Gas counter
Value=1: H2O cold counter
Value=2: H2O hot counter
Value=3: H2O hot KWh counter
Value=4: External counter
Value=5: REM (remote function)
All other values are considered as
value=0
304389
1124h 1 Digital input 1 prescaler
UINT 16
304390
1125h 1 Digital input 2 prescaler
UINT 16
304391
1126h 1 Digital input 3 prescaler
UINT 16
Value min = 1
Value max = 9999
If the value is outside the limits
the instrument considers that the
value is equal to 1
304404
1133h 1 Digital input 1 format UINT 16
304405
1134h 1 Digital input 2 format UINT 16
304406
1135h 1 Digital input 3 format UINT 16
Value=0: 3 decimal digits
Value=1: 2 decimal digits
Value=2: 1 decimal digit
304392
1127h 1 Tariff managed via serial
communication
UINT 16 Writing in this cell, the multi-
tariff can be managed via serial
communication, excluding any
influence of the digital
inputs(only if the digital inputs
are not set to tariff selection).
To set a tariff, a frame including
the following information is to be
sent. LSB: 5Ah al
ways; MSB: tariff
(value from 0 to 3).
NOTES:
a) Except for external meters, if 2 or more digital inputs are linked to the same meter, it is
enabled only the first meter having that selection.
b) If 2 inputs are set in Sync mode, the switching of any of the inputs is considered as a
synchronisation signal.
c) If only one of the inputs is set in Tariff mode, only tariffs 1 and 2 are managed.
d) If the tariff is selected by RS485, only the 4 tariff mode is managed.