Key-pad
NOTE
CARLO GAVAZZI
A
utomation Components
120 RS232-458: This function allows the user to set the RS232 and RS485
serial communication ports (MC232485 module).
130 ETHERNET: This function allows the user to set the Ethernet commu-
nication port. In case of BACnet IP port, the BACnet instance number can
only be programmed by WM3040Soft programming software.
140 BACNET 485: This function allows the user to set the BACnet MS/TP
parameters. The BACnet instance number can only be programmed by
WM3040Soft programming software.
150 VIRT AL 1: This function allows you to set the alarm parameters. 151
ENABLE: enable (YES) or disable (NO) the alarm. 152 VARIABLES: set the
variable to be linked to the alarm. 153 SET 1:set the on alarm set point of
the variable. 154 SET 2: set the off alarm set point of the variable. 155 ON
DELAY: set a delay on activation of the alarm.
190 DIG OUT 1: This function allows to link a virtual alarm to the digital
output and to its working parameters. 191 FUNCTION: Alarm, the digital
output is enabled only if the expected alarm status occurs. Pulse, the
measured energy is retransmitted by the digital output by means of puls-
es.
Remote, the digital output can be enabled through a command sent by
means of serial communication port. 192 AL LINK: select the virtual alarm
to which it has to be linked. 193 AL STATUS: “ND” (normally de-energized
r
elay) or “NE” (normally energized relay) 195 PULSE WEIG: selects the
pulse weight (kWh per pulse). 196 OUT TEST: enables the TEST (YES), dis-
ables the TEST (NO). 197 POWER TEST: sets the simulated power value
(kW) to which a pr
oportional pulse sequence accor
ding to “PULSE WEIG”
corresponds. The function is active until you remain within the menu and
it is used when the output is connected to a PLC.
Some specific menus display only if the relevant modules are
installed.