Key-pad
NOTE
CARLO GAVAZZI
A
utomation Components
210 AN OUT 1: this submenu allows the programming of the analogue
outputs (0-20mA, 0-10V). 211 VARIABLES: select the variable to be
retransmitted by means of the analog output.
212 MIN INPUT: minimum
value of the variable input range to which the “MIN OUTPUT” value,
retransmitted by the analogue output, will be linked.
213 MAX INPUT:
maximum value of the variable input range to which the “MAX OUTPUT”
value, retransmitted by the analogue output, will be linked. 214 MIN OUT-
PUT: set the value expressed as % of the output range (0-20mA, 0-10V) to
be linked to the minimum measured value.
215 MAX OUTPUT: select the
value expressed as % of the output range (0-20mA, 0-10V) to be linked to
the maximum measured value.
230 METERS: reset the ENERGY METERS choosing among: TOTAL,
PARTIAL: resets all energy meters, both total and partial. TOTAL +: resets
the total meters of imported ener
gy
. TOT
AL -: resets the total meters of
exported energy. PARTIAL +: resets the partial meters of imported energy.
PARTIAL -: resets the partial meters of exported energy.
240 RESET: carry out the reset of the MAX or dmd stored values.
250 CLOCK, 241 FORMAT: UE, set the European time format as 24h
(00:00) or the USA set the American time format as 12h (12:00 AM/PM).
252 YEAR: set the current year. 253 MONTH: set the current month.
254 DAY: set the current day. 255 HOUR: set the current hour.
256 minute: set the current minute. 257 SECOND: set the current second.
Some specific menus display only if the relevant modules are
installed.
12
P
ush for at
least 2 s
Page 10 (200)
Save the set
parameters and come
back to the measuring
mode.
L
ist of available
variables
As AN OUT 1
Page 7 (10)