Operating instructions

IN
I
3"MIN
I
C99020
Fig. 9_Sediment Trap
2. Remove return duct cover located on duct panel by breaking
connecting tabs with screwdriver and a hammer (See Fig. 10A
& 10B).
3. To remove supply duct cover, break front and tight side
connecting tabs with a screwdriver and a hammer. Push louver
down to break rear and left side tabs (See Fig. 10A & 10B).
4. If unit ductwork is to be attached to veztical opening flanges
on the unit composite base (jackstand applications only), do so
at this time.
5. It is recommended that the unit base insulation around the
perimeter of the vertical return-air opening be secured to the
unit base with aluminum tape. Applicable local codes may
require aluminum tape to prevent exposed fiberglass.
6. Cover both horizontal duct openings with the duct covers from
the accessory duct cover kit. Ensure opening is air- and
watertight.
- t
.I
,=T---
SUPPLY RETURN
DUCT DUCT
OPENING OPENING
C99011
Fig. 10A Supply and Return Duct Opening
DUCTCOVERSREMOVED
C99012
Fig. 10B--Vertical Duct Cover Removed
7. After completing unit conversion, perform all safety checks
and power up unit.
NOTre: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence-type air conditioning and ventilating systems, NFPA
90A or residence-type, NFPA 90B; and/or local codes and
ordinances.
Adhere to the following criteria when selecting, sizing, and
installing the duct system:
1. Units are shipped for horizontal duct installation (by removing
duct covers).
2. Select and size ductwork, supply-air registers, and return-air
grilles according to American Society of Heating, Refrigera-
tion and Air Conditioning Engineers (ASHRAE) recommen-
dadons.
3.
4.
Use flexible transition between rigid ductwork and unit to
prevent transmission of vibration. The transition may be
screwed or bolted to duct flanges. Use suitable gaskets to
ensure weathertight and airtight seal.
All units must have field-supplied filters or accessory fdter
rack installed in the return-air side of the unit. Recommended
sizes for filters are shown in Tables 1 and 2.
5.
6.
7.
Size all ductwork for maximum required airflow (either
heating or cooling) for unit being installed. Avoid abrupt duet
size increases or decreases or performance may be affected.
Adequately insulate and weatherproof all ductwork located
outdoors. Insulate ducts passing through unconditioned space,
and use vapor barrier in accordance with latest issue of Sheet
Metal and Air Conditioning Contractors National Association
(SMACNA) and Air Conditioning Contractors of America
(ACCA) minimum installation standards for heating and air
conditioning systems. Secure all ducts to building structure.
Flasli, weatherproof, and vibration-isolate all openings in
building structure in accordance with local codes and good
building practices.
11