Operating instructions

Step 10--INSTALL ELECTRICAL CONNECTIONS
r._l LI"/_-'1,'I I",[_
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of serious injury
if an electrical fault should occur. This ground may consist of
an electrical rare connected to the unit ground lug in the
control compartment, or conduit approved for electrical
ground when installed in accordance with NEC (National
Electrical Code) ANSI/NFPA (latest edition) and local elec-
trical codes. In Canada, follow Canadian Electrical Code
CSA (Canadian Standards Association) C22.1 and local
electrical codes. Failure to adhere to this warning could re.cull
in serious injury or death.
Failure to follow these precautions could result in damage to
the unit being installed:
1. Make all electrical connections in accordance with NEC
ANSI/NFPA (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical connec-
tions must be in accordance with CSA standard C22.1
Canadian Electrical Code Part 1 and applicable local
codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating
voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc. On
3-phase units, ensure phases are balanced within 2 percent.
Consult local power company for correction of improper
voltage and/or phase imbalance.
r!_kvl:1:]_llTI
HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field-
supplied, waterproof, disconnect switch mounted at, or within
sight from, the unit. Refer to the unit rating plate for maximum
fllse/circdit breaker size and minimum circuit amps (ampacity) for
wire sizing (See Tables 4 and 5 for electrical data).
The lleld-supplied disconnect switch box may be mounted on the
unit over the high-voltage inlet hole when the standard power and
low-voltage entry points are used (See Fig. 2 and 3 for acceptable
location).
See unit wiring label and Fig. 11 for reference when making high
voltage connections. Proceed as follows to complete the high-
voltage connections to the unit.
I. Run the high-voltage (LI, L2, L3) and ground leads into the
control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the lines side
of the contactor.
4. Connect field L1 to black wire on connection 11 of the
compressor contactor.
5. Connect field wire L2 to yellow wire on connection 13 of the
compressor contactor.
6. Connect field wire L3 to Blue wire from compressor.
12
/_
HIGH VOLTAGE r - - -
POWER LEADS l_ _o-
(SEE UNIT WIRING
LABEL)
GND
CONTROL BOX
LOW-VOLTAGE _i
POWER LEADS_
(SEE UNIT
WIRING LABEL)
SPLICE BOX
FIELD-SUPPLIED
FUSED DISCONNECT
II
_GRN_(G_) _yEpIRc_A_O_TAT
C99018
Fig. 11--High- and Control-Voltage connections
SPECIAL PROCEDURES FOR 208-V OPERATION
Before making any wiring changes, make sure the gas supply
is switched off first. Then switch off the power supply to the
unit and install lockout tag. Electrical shock can cause serious
Injury or death.
CONTROL VOLTAGE CONNECTIONS
Do not use any type of power-stealing thermostat. Unit control
problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated
(35 C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
more than 100 ft from the unit (as measured along the control
voltage wires), use no. 16 AWG color-coded, insulated (35 C
minimum) wires.
Standard Connection
Remove knockout hole located in the flue panel adjacent to the
control access panel (See Fig. 2 and 3). Remove the rubber
grommet from the installer's packet (included with unit) and install
grommet in the knockout opening. Provide a drip loop before
running wire through panel.
Run the low-voltage leads from the thermostat, through the inlet
hole, and into unit low-voltage splice box.
Locate five 18-gage wires leaving control box. These low-voltage
connection leads can be identified by the colors red, green, yellow,
brown, and white (See Fig. 11). Ensure the leads are long enough
to be routed into the low-voltage splice box (located below fight
side of control box). Route leads through hole in bottom of control
box and make low-voltage connections (See Fig. 11). Secure all
cut wires, so that they do not interfere with operation of unit.
HEAT ANTICIPATOR SETTING
The room thermostat heat anticipator must be properly adjusted to
ensure proper heating performance. Set the heat anticipator, using
an ammeter between the W and R terminals to determine the exact
required _tdng.
NOTE: For thermostat selection purposes, use 0.18 amp for the
approximate required setting. Failure to make a proper heat
anticipator adjustment will result in improper operation, discom-
fort to the occupants of the conditioned space, and inefficient
energy utilization; however, the required setting may be changed
slightly to provide a greater degree of comfort for a particular
installation.