Product data

Physical data
NOMINAL
CAPACITY
TONS (kW)
COOLER CONDENSER
ECONOMIZER
COMPRESSOR
UNIT
MOUNTED
STARTER
TOTAL
DRY WEIGHT
REFRIGERANT
WEIGHT*
TOTAL
OPERATING
WEIGHT
60 Hz 50 Hz Size Frame Size Frame Size VI lb kg lb kg lb kg
150
(530)
130
(460)
10,11 1 10,11 1 N C2 0 or 1
Y 9,750 4423 600 272 11,055 5015
N 9,250 4196 600 272 10,555 4788
185
(650)
150
(530)
10,11 1 10,11 1 N C4 0
Y 9,750 4423 600 272 11,055 5015
N 9,250 4196 600 272 10,555 4788
200
(700)
165
(580)
10,11 1 10,11 1 Y C4 0 or 1
Y 10,050 4559 650 295 11,410 5176
N 9,550 4332 650 295 10,910 4949
230
(810)
190
(670)
20,21 2 20,21 2 N C6 0
Y 10,630 4822 700 318 12,210 5538
N 10,130 4595 700 318 11,710 5312
250
(880)
205
(720)
20,21 2 20,21 2 Y C6 0 or 1
Y 10,930 4958 750 340 12,560 5697
N 10,430 4731 750 340 12,060 5470
NOMINAL
CAPACITY
TONS (kW)
COOLER CONDENSER
ECONOMIZER
COMPRESSOR
UNIT
MOUNTED
STARTER
TOTAL
DRY WEIGHT
REFRIGERANT
WEIGHT*
TOTAL
OPERATING
WEIGHT
60 Hz 50 Hz Size Frame Size Frame Size VI lb kg lb kg lb kg
275
(968)
230
(810)
40 4 40 4 N D4 0 or 1
Y 16,110 7307 900 408 17,850 8097
N 15,610 7080 900 408 17,350 7870
300
(1056)
250
(880)
41 4 41 4 Y D4 0 or 1
Y 16,915 7672 1100 499 18,940 8592
N 16,415 7445 1100 499 18,440 8365
325
(1144)
270
(950)
42 4 42 4 N D6 0 or 1
Y 16,730 7588 1100 499 18,860 8555
N 16,230 7361 1100 499 18,360 8328
360
(1270)
300
(1060)
43 4 43 4 Y D6 0 or 1
Y 17,585 7976 1300 590 20,020 9081
N 17,085 7749 1300 590 19,520 8855
LEGEND
NIH Nozzle-In-Head
MWB Marine Waterbox
VI Volumetric Index
*Indicates HCFC-22 refrigerant.
NOTES:
1. Frame 1 and 2 machine weights are based on 2-pass, 150 psig
(1034 kPa) heat exchangers with 0.035 in. wall thickness and cop-
per tubes. Add Refrigerant Weight to Total Dry Weight to obtain Rig-
ging Weight with factory charge.
2. Frame 4 machine weights are based on 2-pass, 150 psig (1034 kPa),
NIH waterbox arrangements with 0.025 in. wall thickness and Turbo-B2
tubes. To calculate Frame 4 MWB vessel weight, refer to the com-
puter selection program.
3. To obtain chiller weights on Frame 4 machines using HFC-134a
refrigerant, refer to the Computer Selection Program or contact
Syracuse.
4. All weights are given for reference only. Refer to the computer se-
lection program for specific machine configuration weights.
13