Product data

Electrical data
COMPRESSOR
MOTOR
ELECTRICAL
CHARACTERISTICS
60 Hz MOTORS 50 Hz MOTORS
Low Voltage Low Voltage
Size VI Type
Max
208 V 230 V 400 V 460 V 575 V
Max
346 V 400 V
IkW IkW
C2 0
RLA per IkW
125
3.01 2.86 1.61 1.39 1.12
125
1.86 1.62
LRA Wye 789 713 388 331 269 387 333
LRA Delta 2465 2229 1212 1035 840 1210 1041
C4
0
RLA per IkW
155
3.04 2.95 1.61 1.38 1.12
155
1.88 1.61
LRA Wye 1026 928 475 390 323 473 390
LRA Delta 3206 2899 1485 1217 1010 1478 1220
1
RLA per IkW
195
2.97 2.73 1.59 1.36 1.09
195
1.86 1.58
LRA Wye 990 896 566 448 358 563 451
LRA Delta 3095 2799 1770 1399 1120 1759 1410
C6 0or1
RLA per IkW
195
2.97 2.73 1.59 1.36 1.09
195
1.86 1.58
LRA Wye 990 896 566 448 358 563 451
LRA Delta 3095 2799 1700 1399 1120 1759 1410
D4, D6 0 or 1
RLA per IkW
280
3.04 2.74 1.61 1.40 1.12
280
1.87 1.61
LRA Wye 1530 1325 798 662 529 779 652
LRA Delta 4780 4139 2493 2070 1853 2435 2038
LEGEND
IkW Compressor Motor Power Input (Kilowatts)
LRA Locked Rotor Amps
OLTA Overload Trip Amps (= RLA x 1.08)
RLA Rated Load Amps
VI Volumetric Index
NOTES:
1. Standard Voltages:
60 Hz 50 Hz
Volt
For Use on
Supply Voltages
Volt
For Use on
Supply Voltages
208/230* 200 to 240 v systems 346 320 to 360 v systems
200† 200 to 208 v systems 400 380 to 415 v systems
230† 220 to 240 v systems
400 360 to 429 v systems
460 440 to 480 v systems
575 550 to 600 v systems
*Available on Frame 1 and 2 units.
†Available on Frame 4 units.
Motor nameplates can be stamped for any voltage within the listed
supply voltage range. Chillers shall not be selected at voltages above
or below the listed supply voltage range.
2. To establish electrical data for your selected voltage, if other than
listed voltage, use the following formula:
listed voltage
RLA = listed RLA x
selected voltage
listed voltage
OLTA = listed OLTA x
selected voltage
selected voltage
LRA = listed LRA x
listed voltage
Example: Find the rated load amperage for a 575-v motor listed at
1.14 amps per kW input for use at 550 volts.
575
RLA = 1.14 x = 1.19
550
AUXILIARY RATINGS (115 V, 1 Phase, 50/60 Hz)
ITEM POWER
SEALED
KVA
AVERAGE
WATTS
CONTROLS 24 vdc 0.16 160
OIL HEATER* 115-230/1/60 500
*Frame 1 and 2 machines.
Compressor motor controllers
Compressor motors, controls, and accessories require the
use of starting equipment systems specifically designed for
23 Series Chillers. Refer to Carrier Engineering Require-
ment Z-375.
Capacitors/power factors
Power factor considerations may indicate use of capacitors.
Properly sized capacitors improve power factors, especially
at part load. Contact your local Carrier sales representative
for further information on power factors.