Product data

Guide specifications (cont)
J. Insulation:
1. Chilled water piping and cooler waterboxes shall
be insulated by the mechanical contractor.
2. Factory installed insulation shall be available for
the chiller. Additional insulation shall be installed
at the jobsite by the mechanical contractor.
3. Chillerinsulation shall be
3
4
-in.thick and shall have
a thermal conductivity not exceeding 0.28 Btu
in./hr sq ft F and shall conform to UL Stand-
ard 94, Classification 94 HBF.
K. Vibration Isolation:
Chiller manufacturer shall furnish neoprene isolator
pads for mounting equipment on a level concrete
surface.
L. Start-Up:
1. The chiller manufacturer shall provide a factory-
trained representative, employed by the chiller
manufacturer, to perform the start-up procedures
as outlined in the start-up, operation, and
maintenance manual provided by the chiller
manufacturer.
2. After the above services have been performed, the
same factory-trained representative shall be avail-
able for a period of classroom instruction (not to
exceed 4 hours) to instruct the chiller owner’s per-
sonnel in the proper operation and maintenance
of the chiller.
3. Manufacturer shall supply the following literature:
a. Start-Up, Operation, and Maintenance
Instructions.
b. Installation Instructions.
c. Field Wiring Diagrams.
d. One complete set of certified drawings.
M. Optional Field Installed Accessories:
The following standard accessories are available for
field installation:
1. Soleplate Package
2. Spring Isolators
3. Spare Sensor Package
4. Control Options Module Upgrade Kit
5. Stand-Alone Pumpout Unit
6. Separate Storage Tank and Pumpout Unit
7. Flow Switch, Differential Pressure Type
8. Sound Insulation Kit
9. Refrigerant Isolation Package
10. Automatic Hot Gas Bypass
11. Low Voltage Unit-Mounted Starter (Wye-Delta,
Solid State)
12. Low Voltage Remote Motor Starter (Wye-Delta,
Solid State)
13. Field Mounting Kit for Unit-Mounted Starters
N. Factory Installed Options:
1. Thermal Insulation
2. Automatic Hot Gas Bypass
3. Control Options Module
4. Cooler/Condenser Tubing Options
5. Cooler and Condenser Passes
6. Nozzle-In-HeadWaterboxes,300 psig(2067 kPa)
(Select Sizes)
7. Marine Waterboxes, 300 psig (2067 kPa) (select
sizes)
8. Refrigerant Isolation Package
9. Factory Performance Test
10. Low Voltage Unit-Mounted Starter (Wye-Delta,
Solid State)
11. Export Crating
12. Factory Charged Unit