Installation manual
38GL...G9 / 38YY...G9 / 38YYS...G9
Cooling only and heat pump split system outdoor units
GB - 1
ENGLISH
For operation and maintenance instructions of this unit as well as installation
instructions of the indoor unit, refer to the relevant manuals.
Contents
Page
Dimensions and weight ................................................................................................................. 2
Connections .................................................................................................................................. 2
Minimum clearances ..................................................................................................................... 3
Operating limits ............................................................................................................................. 3
General information....................................................................................................................... 4
Warnings: avoid............................................................................................................................. 5
Refrigerant connections ................................................................................................................ 6/8
Electrical connections ................................................................................................................... 9/10
Electrical data ................................................................................................................................10
Pump Down and check the refrigerant charge ............................................................................. 11
Unit maintenance .......................................................................................................................... 12
Troubleshooting............................................................................................................................. 12
Installation instructions supplement ............................................................................................. 13-14
ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
AIR CONDITIONER WITH R-410A–QUICK REFERENCE GUIDE
• R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing
equipment and replacement components are designed to operate with R-410A.
• R-410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a vertical
position with the valve at the top.
• R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device
in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit.
• R-410A, as other HFCs, is only compatible with oils selected by the compressor manufacturer.
• A vacuum pump is not enough to remove moisture from oil.
• Oils absorb moisture rapidly. Do not expose oil to atmosphere.
• Never open system to atmosphere while it is under vacuum.
• When the system must be opened for service, break vacuum with dry nitrogen and replace filter
driers.
• Do not vent R-410A into the atmosphere.
• Use only Carrier matching indoor units (Table I).
Unit size Oil type
Quantity Drier already installed on
cc liquid line of the unit
018 - 024 POE 1120
YES
028 - 036 - 048 POE 1250
YES
052 POE 1660
YES
060 POE 1950
YES
Table I
Cooling Heat
Power
only pump Hi-Wall Console Cassette Satellite
(A/C) (H/P)
supply
38GL018G9 — 42PHQ018N 42PHQ018P
42VMC018(A)*N
40KMC018N 40SMC018N 40DMC018
38GL024G9 — 42PHQ024N 42PHQ024P
42VMC024(A)*N
40KMC024N 40SMC024N 40DMC024
38GL028G9 38YY(S)28G9 — — 42VMC028 40KMC028N 40SMC028N 40DMC028
38GL036G9 38YY(S)36G9 — — 42VMC036 40KMC036N 40SMC036N
40DMC036
400V 3N~50Hz
38GL048G9 38YY(S)48G9 — — — —
40SMC048N
38GL052G9 38YY-052G9 — — — — 40DMC052
38GL060G9
38YY(S)060G9
— — 42VMC048 40KMC048N 40SMC048N 40DMC048
*(A)= Aluminium version