Installation manual

40 GKX
GB - 3
ENGLISH
Technical data
Table V: Operating limits
Cooling / Heating Refer to outdoor unit installation manual.
Nominal single-phase voltage 230V
~
50Hz
60Hz Special Export Market
Main power supply Operating voltage limits min. 198V – max. 264V min. 187V – max. 253V
Nominal three-phase voltage 400V 3N
~
50Hz
Operating voltage limits min. 342V – max. 462V
• For power supply wire size and delay type fuses, refer to the outdoor unit installation instructions.
Note: 230V ~ 50Hz.
Table I: Nominal data
POWER INPUT
Cooling only
Cooling (W) Heating (W)
40GKX012---703 75
40GKX018---703 80
40GKX024---703 105
40GKX028---703 108
40GKX036---703 140
40GKX048---703 185
40GKX060---703 230
40GKX112W--703 75 1575
40GKX118W--703 80 2580
40GKX124W--703 105 2605
40GKX128W--703 108 3108
40GKX136W--703 140 3140
40GKX148W--703 185 3185
40GKX160W--703 230 3230
POWER INPUT
Heat pump
Cooling (W) Heating (W)
40GKX012---703 75 75
40GKX018---703 80 80
40GKX024---703 105 105
40GKX028---703 108 108
40GKX036---703 140 140
40GKX048---703 185 185
40GKX060---703 230 230
40GKX112W--703 75 1575
40GKX118W--703 80 1580
40GKX124W--703 105 1605
40GKX128W--703 108 2108
40GKX136W--703 140 2140
40GKX148W--703 185 2185
40GKX160W--703 230 2230
Model R C Y O
(1)
W2
(1)
S1
(1)
S2
(1)
from 12 to 60 1.0 1.0 1.0 1.0 1.0 0.75 0.75
The power supply cable to the electric heaters must be H07 RN-F type.
The connection cables between indoor and outdoor units must be:
- type A05 RN-F (3 x 1) (R - C -Y) for cooling only units (A/C)
- type A05 RN-F (2 x 1) (R - C) for heat pump units (H/P)
- type A05 RN-F (3 x 1) (Y - O - W2)for heat pump units (H/P)
- type A05 RN-F (2 x 0,75) (S1 - S2)for heat pump units (H/P)
Table II: Connection wire size between indoor and outdoor units (mm
2
)
(1)
Heat pump unit only
Table III: Technical data of electric heaters (if installed)
Heat pump Cooling only
Model 12 18 24 28 36 48 60 12 18 24 28 36 48 60
Electric heater kW 1.5 1.5 1.5 2 x 1.0 2 x 1.0 2 x 1.0 2 x 1.0 1.5 1.5 1.5 2 x 1.0 2 x 1.0 2 x 1.0 2 x 1.0
++++++
capacity
1.0 1.0 2 x 0.5 2 x 0.5 2 x 0.5 2 x 0.5
Supply V 230 230 230 230 230 230 230 230 230 230 400 400 400 400
voltage (ph) (1 ph) (1 ph) (1 ph) (1 ph) (1 ph) (1 ph) (1 ph) (1 ph) (*) (*) (*) (*) (*) (*)
Max. current draw A 6.5 6.5 6.5 8.7 8.7 8.7 8.7 6.5 10.8 10.8 7.5 7.5 7.5 7.5
Control device INTERNEC electronic control
Safety thermostat
N° 1Automatic reset thermostat
N° 1 Manual reset thermostat (electric)
Power supply cables mm
2
3 x 1.5 3 x 1.5 3 x 1.5 4 x 1.5 4 x 1.5 4 x 1.5 4 x 1.5 3 x 1.5 3 x 2.5 3 x 2.5 5 x 1.5 5 x 1.5 5 x 1.5 5 x 1.5
Recommended fuse (gL type) A 8 8 8 10 10 10 10 8 12 12 10 10 10 10
*
In areas with a 2 kW limit for single-phase electric heaters it is possible to divide the power supply on two phases and neutral of a three phase supply with neutral.
Use cable type HO7 RN-F - 4 x 1.5 mm
2
- 400V 2N~
Description Quantity Use
Installation instructions 1 Indoor unit installation
Owner's Manual 1 Correct use
Fresh air intake baffle 1 Air renewal
Table IV:
Material supplied