Operating instructions

130
APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — SERVICE TEST
ITEM EXPANSION UNITS RANGE COMMENT
WRITE
STATUS
CCN TABLE CCN POINT
PAGE
NO.
TEST MANUAL TEST MODE Remote-Off-
Enable Switch
must be set to
OFF Position
SERV_TST
T.REQ Manual Sequence OFF/ON forcible SERV_TST
Q_STREQ
77,
104,
105
CP.A Compressor A Output OFF/ON Remote-Off-
Enable Switch
must be set to
ENABLE
Position
forcible SERV_TST
Q_CPA
77,78
SLI.A Slide Valve Capacity A unchanged
increase
decrease
forcible SERV_TST Q_SLIA
CP.B Compressor B Output OFF/ON forcible SERV_TST Q_CPB 77,78
SLI.B Slide Valve Capacity B unchanged
increase
decrease
forcible SERV_TST Q_SLIB
CP.C Compressor C Output OFF/ON forcible SERV_TST Q_CPC 77,78
SLI.C Slide Valve Capacity C unchanged
increase
decrease
forcible SERV_TST Q_SLIC
QUIC QUICK TEST MODE Remote-Off-
Enable Switch
must be set to
OFF Position
QCK_TST1
Q.REQ OFF/ON forcible QCK_TST1
Q_TSTRQ
104,
106
EXV.A Circuit A EXV % Open XXX (%) 0-100 forcible QCK_TST1 Q_EXVA 76,77
EXV.B Circuit B EXV % Open XXX (%) 0-100 forcible QCK_TST1 Q_EXVB 76,77
EXV.C Circuit C EXV % Open XXX (%) 0-100 forcible QCK_TST1 Q_EXVC 76,77
ECO.A Circ A ECO EXV % XXX (%) 0-100 forcible QCK_TST1 Q_ECO_A 77
ECO.B Circ B ECO EXV % XXX (%) 0-100 forcible QCK_TST1 Q_ECO_B 77
ECO.C Circ C ECO EXV % XXX (%) 0-100 forcible QCK_TST1 Q_ECO_C 77
FAN.A Circuit A Fan Stages X 0-8 forcible QCK_TST1 Q_FAN_A
FAN.B Circuit B Fan Stages X 0-8 forcible QCK_TST1 Q_FAN_B
FAN.C Circuit C Fan Stages X 0-8 forcible QCK_TST1 Q_FAN_C
SPD.A
Cir A Varifan position XXX (%) 0-100 forcible QCK_TST1 Q_VFANA
SPD.B Cir B Varifan position XXX (%) 0-100 forcible QCK_TST1 Q_VFANB
SPD.C Cir C Varifan position XXX (%) 0-100 forcible QCK_TST1 Q_VFANC
HT.A Oil Heater Circuit A OFF/ON forcible QCK_TST1 Q_HT_A
SL1.A Slide Valve 1 Cir A OFF/ON forcible QCK_TST1 Q_SLI_1A
SL2.A Slide Valve 2 Cir B OFF/ON forcible QCK_TST1 Q_SLI_2A
HGP.A Hot Gas Bypass A Output OFF/ON forcible QCK_TST1 Q_HGBP_A
OLS.A Oil Solenoid Cir A OFF/ON forcible QCK_TST1 Q_OILS_A
DGT.A DGT Cool Solenoid A OFF/ON forcible QCK_TST1 Q_CDGT_A
HT.B Oil Heater Circuit B OFF/ON forcible QCK_TST1 Q_HT_B
SL1.B Slide Valve 1 Cir B OFF/ON forcible QCK_TST1 Q_SLI_1B
SL2.B Slide Valve 2 Cir B OFF/ON forcible QCK_TST1 Q_SLI_2B
HGP.B Hot Gas Bypass B Output OFF/ON forcible QCK_TST1 Q_HGBP_B
OLS.B Oil Solenoid Cir A OFF/ON forcible QCK_TST1 Q_OILS_B
DGT.B DGT Cool Solenoid B OFF/ON forcible QCK_TST1 Q_CDGT_B
HT.C Oil Heater Circuit C OFF/ON forcible QCK_TST1 Q_HT_C
SL1.C Slide Valve 1 Cir C OFF/ON forcible QCK_TST1 Q_SLI_1C
SL2.C Slide Valve 2 Cir C OFF/ON forcible QCK_TST1 Q_SLI_2C
HGP.C Hot Gas Bypass C Output OFF/ON forcible QCK_TST1 Q_HGBP_C
OLS.C Oil Solenoid Cir C OFF/ON forcible QCK_TST1 Q_OILS_C
DGT.C DGT Cool Solenoid C OFF/ON forcible QCK_TST1 Q_CDGT_C
PMP.1 Water Exchanger Pump 1 OFF/ON forcible QCK_TST1 Q_PMP1
PMP.2 Water Exchanger Pump 2 OFF/ON forcible QCK_TST1 Q_PMP2
PMP.3 Condenser Pump 1 OFF/ON forcible QCK_TST1 Q_HPMP1
CL.HT Cooler Heater Output OFF/ON forcible QCK_TST1 Q_CL_HT
BVL.A Ball Valve Position A OPEN/CLSE forcible QCK_TST1 Q_BVL_A
BVL.B Ball Valve Position B OPEN/CLSE forcible QCK_TST1 Q_BVL_B
BVL.C Ball Valve Position C OPEN/CLSE forcible QCK_TST1 Q_BVL_C
Q.RDY Chiller Ready Status OFF/ON forcible QCK_TST1 Q_READY
Q.RUN Chiller Running Status OFF/ON forcible QCK_TST1 Q_RUN
SHUT Customer Shutdown Stat OFF/ON forcible QCK_TST1 Q_SHUT
CATO Chiller Capacity in 0-10v XX.X (vdc) 0-10 forcible QCK_TST1 Q_CATO
ALRM Alarm Relay OFF/ON forcible QCK_TST1 Q_ALARM
ALRT Alert Relay OFF/ON forcible QCK_TST1 Q_ALERT