Operating instructions

134
APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — OUTPUTS
ITEM EXPANSION UNITS RANGE COMMENT
WRITE
STATUS
CCN TABLE CCN POINT
PAGE
NO.
CIR.A CIRCUIT A OUTPUTS
CP.A Compressor A Relay OFF/ON CIRCA_D CP_A 12
HT.A Oil Heater Circuit A OFF/ON CIRCA_D OIL_HT_A 10,12
SL1.A Slide Valve 1 Cir A OFF/ON CIRCA_D SLID1_A 12
SL2.A Slide Valve 2 Cir A OFF/ON CIRCA_D SLID2_A 12
OLS.A Oil Solenoid Cir A OFF/ON CIRCA_D OIL_SL_A 12
HGB.A Hot Gas Bypass Cir A OFF/ON CIRCA_D 19
FAN.A Circuit A Fan Stages X 0-6 CIRCA_D FAN_ST_A
SPD.A Circ A Varifan Position XXX (%) 0-100 CIRCA_AN hd_pos_a 16
EXV.A Circuit A EXV % Open XXX (%) 0-100 CIRCA_AN EXV_A 14,76
ECO.A Circ A EXV ECO % Open XXX (%) 0-100 CIRCA_AN EXV_EC_A 14
DGT.A DGT Cool Solenoid A OFF/ON CIRCA_D dgt_gascool_a 12
CIR.B CIRCUIT B OUTPUTS
CP.B Compressor B Relay OFF/ON CIRCB_D CP_B 12
HT.B Oil Heater Circuit B OFF/ON CIRCB_D OIL_HT_B 10,12
SL1.B Slide Valve 1 Cir B OFF/ON CIRCB_D SLID1_B 12
SL2.B Slide Valve 2 Cir B OFF/ON CIRCB_D SLID2_B 12
OLS.B Oil Solenoid Cir B OFF/ON CIRCB_D OIL_SL_B 12
HGB.B Hot Gas Bypass Cir B OFF/ON CIRCB_D 19
FAN.B Circuit B Fan Stages X 0-6 CIRCB_D FAN_ST_B
SPD.B Circ B Varifan Position XXX (%) 0-100 CIRCB_AN hd_pos_b 16
EXV.B Circuit B EXV % Open XXX (%) 0-100 CIRCB_AN EXV_B 14,76
ECO.B Circ B EXV ECO % Open XXX (%) 0-100 CIRCB_AN EXV_EC_B 14
DGT.B DGT Cool Solenoid B OFF/ON CIRCB_D dgt_gascool_b 12
CIR.C CIRCUIT C OUTPUTS
CP.C Compressor C Relay OFF/ON CIRCC_D CP_C 12
HT.C Oil Heater Circuit C OFF/ON CIRCC_D OIL_HT_C 12
SL1.C Slide Valve 1 Cir C OFF/ON CIRCC_D SLID1_C 12
SL2.C Slide Valve 2 Cir C OFF/ON CIRCC_D SLID2_C 12
OLS.C Oil Solenoid Cir C OFF/ON CIRCC_D OIL_SL_C 12
HGB.C Hot Gas Bypass Cir C OFF/ON CIRCC_D 19
FAN.C Circuit C Fan Stages X 0-6 CIRCC_D FAN_ST_C
SPD.C Circ C Varifan Position XXX (%) 0-100 CIRCC_AN hd_pos_c 16,17
EXV.C Circuit C EXV % Open XXX (%) 0-100 CIRCC_AN EXV_C 14,76
ECO.C
Circ C EXV ECO % Open XXX (%) 0-100 CIRCC_AN EXV_EC_C 14
DGT.C DGT Cool Solenoid C OFF/ON CIRCC_D dgt_gascool_c 12
GEN.O GENERAL OUTPUTS
PMP.1 Water Exchanger Pump 1 OFF/ON forcible STATEGEN CPUMP_1 19
PMP.2 Water Exchanger Pump 2 OFF/ON forcible STATEGEN CPUMP_2 19
PMP.3 Condenser Pump 1 OFF/ON STATEGEN HPUMP_1
CO.HT Cooler Heater Output OFF/ON STATEGEN COOLHEAT 10
BVL.A Ball Valve Position A OPEN/CLOSE CIRCA_D ref_iso_a 10
BVL.B Ball Valve Position B OPEN/CLOSE CIRCB_D ref_iso_b 10
BVL.C Ball Valve Position C OPEN/CLOSE CIRCC_D ref_iso_c 10
CN.HT Condenser Heat Output OFF/ON Not supported. RECLAIM cond_htr
REDY Chiller Ready Status OFF/ON STATEGEN READY
RUN Chiller Running Status OFF/ON STATEGEN RUNNING 18
SHUT Customer Shutdown Stat OFF/ON STATEGEN SHUTDOWN 18
CATO Chiller Capacity 0-10 v XX.X 0-10 STATEGEN CAPT_010 18
ALRM Alarm Relay OFF/ON STATEGEN ALARM 10
ALRT Alert Relay OFF/ON STATEGEN ALERT 10