Operating instructions

135
APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — CONFIGURATION
*Unit size should be entered as nominal size. For units with DX cooler option,
unit capacity is nominal tonnage i.e., 92 should be 90) and configure DX
cooler equal to yes.
†Must be configured to 1 for the motorized ball valves (ABV) to operate.
**Navigator Display = NO, Touch Pilot Display = YES.
ITEM EXPANSION UNITS RANGE COMMENT DEFAULT
CCN
TABL E
CCN
POINT
PAGE NO.
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs OFF/ON OFF N/A display_test 8
METR Metric Display US/METR US DISPCONF DISPUNIT 7
LANG Language Selection English
Espanol
Francais
Portugues
Translated
English DISPCONF LANGUAGE 8
UNIT UNIT CONFIGURATION
TYPE Unit Type 1 = Air Cooled
2 = Heat Pump
Air cooled FACTORY unit_typ
TONS Unit Size XXX 0 to 1800*
(nominal size)
FACTORY unitsize 100
VAR.A Nb Fan on Varifan Cir A X 0-8 0: No low ambient
temperature head
pressure control
1:low ambient
temperature head
pressure control
0 FACTORY varfan_a
VAR.B Nb Fan on Varifan Cir B X 0-8 0: No low ambient
temperature head
pressure control
1: low ambient
temperature head
pressure control
0 FACTORY varfan_b
VAR.C Nb Fan on Varifan Cir C X 0-8 0: No low ambient
temperature head
pressure control
1: low ambient
temperature head
pressure control
0 FACTORY varfan_c
VOLT Power Supply Voltage XXX (volt) 200, 230, 380,
460, 575
Nameplate value FACTORY voltage
60HZ 60 Hz Frequency NO/YES YES FACTORY freq_60H
STAR Soft Starter Select NO/YES Not supported. FACTORY softstar
Y.D. Wye Delta T Start Select NO/YES FACTORY wye_delt
MTA.A Must Trip Amps Cir A XXX (amps) 0 to 1500 FACTORY cpa_mtac 12,50
R.MT.A Read Must Trip Amps A XXX (amps) 0 to 1500 FACTORY cpa_mtam
MTA.B Must Trip Amps Cir B XXX (amps) 0 to 1500 FACTORY cpb_mtac 12,50
R.MT.B Read Must Trip Amps B XXX (amps) 0 to 1500 FACTORY cpb_mtam
MTA.C Must Trip Amps Cir C XXX (amps) 0 to 1500 FACTORY cpc_mtac 12,50
R.MT.C Read Must Trip Amps C XXX (amps) 0 to 1500 FACTORY cpb_mtam
C.SW.A S1 Config Switch Cir A XXX (amps) 0 to 255 FACTORY cpa_s1_c 12
R.CSA Read S1 Config Switch A XXX (amps) 0 to 255 FACTORY cpa_s1_m
C.SW.B S1 Config Switch Cir B XXX (amps) 0 to 255 FACTORY cpb_s1_c 12
R.CSB Read S1 Config Switch B XXX (amps) 0 to 255 FACTORY cpb_s1_m
C.SW.C S1 Config Switch Cir C XXX (amps) 0 to 255 FACTORY cpc_s1_c 12
R.CSC Read S1 Config Switch C XXX (amps) 0 to 255 FACTORY cpc_s1_m
RECL Heat Reclaim Select NO/YES Not supported. NO FACTORY recl_opt
DX.CL DX Cooler Select NO/YES NO
EMM EMM Module Installed NO/YES NO FACTORY emm_nrcp 97
PAS. E Password Enable ENBL/DSBL ENBL FACTORY pass_enb
PASS Factory Password XXX 1 to 0150 0111 FACTORY fac_pass
CO.HT Cooler Heater Select† 0-2 0-No Heater,
1-Cooler Heater,
2-Future
1 FACTORY heat_sel 67
CON.V Condenser Valve Select NO/YES NO FACTORY cond_val
HGBP Hot Gas Bypass Select NO/YES NO FACTORY hgbp_sel 32,49
MCHX MCHX Exchanger Select NO/YES NO FACTORY mchx_sel
HI.TI High Tiers Display Select NO/YES ** FACTORY highdisp
H.KIT Hydronic Kit Selection NO/YES Not supported. NO FACTORY
PA.N B Cooler Pass Number 1-3 2 FACTORY
VLT VLT Fan Drive Select Not supported. NONE FACTORY
RPM VLT Fan Drive RPM Not supported. 0 FACTORY
H.CON High Condensing Select NO/YES NO FACTORY