APPENDIX G — BACNET COMMUNICATIONS OPTION (cont)
Table G — Network Points List
LEGEND
BACNET
OBJECT ID
POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT NAME
AV:1 Circuit A Fan #1 Hours R hr hr_fana1_1
AV:2 Circuit A Fan #2 Hours R hr hr_fana2_1
AV:3 Circuit A Fan #3 Hours R hr hr_fana3_1
AV:4 Circuit A Fan #4 Hours R hr hr_fana4_1
AV:5 Circuit A Fan #5 Hours R hr hr_fana5_1
AV:6 Circuit A Fan #6 Hours R hr hr_fana6_1
AV:7 Circuit A Fan #7 Hours R hr hr_fana7_1
AV:8 Circuit A Fan #8 Hours R hr hr_fana8_1
AV:9 Circuit A Fan #9 Hours R hr hr_fana9_1
AV:10 Circuit A Fan #10 Hours R hr hrfana10_1
AV:11 Circuit B Fan #1 Hours R hr hr_fanb1_1
AV:12 Circuit B Fan #2 Hours R hr hr_fanb2_1
AV:13 Circuit B Fan #3 Hours R hr hr_fanb3_1
AV:14 Circuit B Fan #4 Hours R hr hr_fanb4_1
AV:15 Circuit B Fan #5 Hours R hr hr_fanb5_1
AV:16 Circuit B Fan #6 Hours R hr hr_fanb6_1
AV:17 Circuit B Fan #7 Hours R hr hr_fanb7_1
AV:18 Circuit B Fan #8 Hours R hr hr_fanb8_1
AV:19 Circuit B Fan #9 Hours R hr hr_fanb9_1
AV:20 Circuit B Fan #10 Hours R hr hrfanb10_1
AV:21 Circuit C Fan #1 Hours R hr hr_fanc1_1
AV:22 Circuit C Fan #2 Hours R hr hr_fanc2_1
AV:23 Circuit C Fan #3 Hours R hr hr_fanc3_1
AV:24 Circuit C Fan #4 Hours R hr hr_fanc4_1
AV:25 Circuit C Fan #5 Hours R hr hr_fanc5_1
AV:26 Circuit C Fan #6 Hours R hr hr_fanc6_1
AV:27 Circuit C Fan #7 Hours R hr hr_fanc7_1
AV:28 Circuit C Fan #8 Hours R hr hr_fanc8_1
AV:29 Compressor Suction Temp R °F suct_t_a_1
AV:30 Compressor Suction Temp R °F suct_t_b_1
AV:31 Compressor Suction Temp R °F suct_t_c_1
AV:32 Discharge Gas Temp R °F dgt_a_1
AV:33 Discharge Gas Temp R °F dgt_b_1
AV:34 Discharge Gas Temp R °F dgt_c_1
AV:35 Discharge Pressure R psi dp_a_1
AV:36 Discharge Pressure R psi dp_b_1
AV:37 Discharge Pressure R psi dp_c_1
AV:38 Economizer Gas Temp R °F eco_tp_a_1
AV:39 Economizer Gas Temp R °F eco_tp_b_1
AV:40 Economizer Gas Temp R °F eco_tp_c_1
AV:41 Economizer Pressure R psi econ_p_a_1
AV:42 Economizer Pressure R psi econ_p_b_1
AV:43 Economizer Pressure R psi econ_p_c_1
AV:44 EXV Position R %
exv_a_1
AV:45 EXV Position R % exv_b_1
AV:46 EXV Position R % exv_c_1
AV:47 Fan Staging Number R fan_st_a_1
AV:48 Fan Staging Number R fan_st_b_1
AV:49 Fan Staging Number R fan_st_c_1
AV:50 Head Pressure Actuator Position R % hd_pos_a_1
AV:51 Head Pressure Actuator Position R % hd_pos_b_1
AV:52 Head Pressure Actuator Position R % hd_pos_c_1
AV:53 Heat/Cool Select R/W
0 = C o o l
1 = H e a t
2=Auto
hc_sel_1
AV:54 Minutes Left for Start R min min_left_1
CHWS Chilled Water Switch EXV Expansion Valve
DGT Discharge Gas Thermistor OAT Outdoor Air Temperature
DO Digital Output R—Read
EWT Entering Water Temperature W—Write