Operating instructions

175
APPENDIX G — BACNET COMMUNICATIONS OPTION (cont)
Table G — Network Points List (cont)
LEGEND
BACNET
OBJECT ID
POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT NAME
AV:104 Water pressure after filter R psi watpres4_1
AV:105 Water flow R gal/sec wat_flow_1
AV:106 Circuit Loading Sequence R/W
0 = Au t o
1 =A Le a d
2 =B Le ad
3=C Lead
lead_cir_1
AV:107 Compressor A Hours R hr hr_cp_a_1
AV:108 Compressor A Starts R st_cp_a_1
AV:109 Compressor B Hours R hr hr_cp_b_1
AV:110 Compressor B Starts R st_cp_b_1
AV:111 Compressor C Hours R hr hr_cp_c_1
AV:112 Compressor C Starts R st_cp_c_1
AV:113 Cooler pump #1 Hours R hr hr_cpum1_1
AV:114 Cooler pump #2 Hours R hr hr_cpum2_1
AV:115 Machine Operating Hours R hr hr_mach_1
AV:116 Machine Starts R st_mach_1
AV:117 Cooler Pumps Sequence R/W
0 = N o P u m p
1 = O n e P u m p O n l y
2=Two Pumps Auto
3=Pump#1 Manual
4=Pump#2 Manual
cpumpseq_1
AV:118 Current Limit at 100% R/W A 0 - 2000 curr_ful_1
AV:119 Pump Auto Rotation Delay R/W hr 24 - 3000 pump_del_1
AV:120 Unit Off-to-On Delay R min off_on_d_1
AV:121 Cooling Ice Setpoint R/W °F 0 ice_sp_1
AV:122 Cooling Ramp Loading R/W °^F 0.2 - 2.0 cramp_sp_1
AV:123 Cooling Reset Degrees R/W °^F -30 - 30 cr_deg_1
AV:124 Cooling Setpoint 1 R/W °F -20 - 70 csp1_1
AV:125 Cooling Setpoint 2 R/W °F -20 - 70 csp2_1
AV:126 Current Full Reset Value R/W mA 0 - 20 v_cr_fu_1
AV:127 Current No Reset Value R/W mA 0 - 20 v_cr_no_1
AV:128 Delta T Full Reset Value R/W °^F 0 - 25 dt_cr_fu_1
AV:129 Delta T No Reset Value R/W °^F 0 - 25 dt_cr_no_1
AV:130 OAT Full Reset Value R/W °F 14 - 125 oatcr_fu_1
AV:131 OAT No Reset Value R/W °F 14 - 125 oatcr_no_1
AV:132 Space T Full Reset Value R/W °F 14 - 125 spacr_fu_1
AV:133 Space T No Reset Value R/W °F 14 - 125 spacr_no_1
AV:134 Switch Limit Setpoint 1 R/W % 0 - 100 lim_sp1_1
AV:135 Switch Limit Setpoint 2 R/W % 0 - 100 lim_sp2_1
AV:136 Switch Limit Setpoint 3 R/W % 0 - 100 lim_sp3_1
AV:137 Alarm State R
0=Normal
1=Partial
2=Shutdown
alm_1
AV:2901 User Defined Analog 1 R/W user_analog_1_1
AV:2902 User Defined Analog 2 R/W user_analog_2_1
AV:2903 User Defined Analog 3 R/W user_analog_3_1
AV:2904 User Defined Analog 4 R/W user_analog_4_1
AV:2905 User Defined Analog 5 R/W user_analog_5_1
AV:9006 System Cooling Demand Level R cool_demand_level_1
AV:80001 System OAT Master R °F mstr_oa_temp_1
CHWS Chilled Water Switch EXV Expansion Valve
DGT Discharge Gas Thermistor OAT Outdoor Air Temperature
DO Digital Output R—Read
EWT Entering Water Temperature W—Write