Operating instructions

CL-3
Record Configuration Information
* Based on Navigator controls.
† Not supported.
TOUCH PILOT™ DESCRIPTION NAVIGATOR™
ITEM
NAVIGATOR
SUBMODE
DEFAULT* ENTRY
None (Navigator Configuration) TEST ConfigurationDISP OFF
Metric Display on STDU METR ConfigurationDISP US
Language Selection LANG ConfigurationDISP English
Unit Type TYPE ConfigurationUNIT Air-Cooled
Unit Capacity Model TONS ConfigurationUNIT Nominal Unit Size
NB Fans on Varifan Cir A VAR.A ConfigurationUNIT 0: No low ambient temperature
head pressure control
1: low ambient temperature
head pressure control installed
NB Fans on Varifan Cir B VAR.B ConfigurationUNIT 0: No low ambient temperature
head pressure control
1: low ambient temperature
head pressure control installed
NB Fans on Varifan Cir C VAR.C ConfigurationUNIT 0: No low ambient temperature
head pressure control
1: low ambient temperature
head pressure control installed
Power Supply Voltage VOLT ConfigurationUNIT Nameplate voltage
Power Frequency 60HZ Sel 60HZ ConfigurationUNIT YES
Soft Starter Select STAR ConfigurationUNIT NO†
Wye Delta Start Select Y.D ConfigurationUNIT Unit Dependent
Must Trip Amps (Circuit A) MTA.A ConfigurationUNIT Unit Dependent
Must Trip Amps (Read Circuit A) R.MT.A ConfigurationUNIT Unit Dependent
Must Trip Amps (Circuit B) MTA.B ConfigurationUNIT Unit Dependent
Must Trip Amps (Read Circuit B) R.MT.B ConfigurationUNIT Unit Dependent
Must Trip Amps (Circuit C) MTA.C ConfigurationUNIT Unit Dependent
Must Trip Amps (Read Circuit C) R.MT.C ConfigurationUNIT Unit Dependent
S1 Config Switch (Circuit A) C.SW.A ConfigurationUNIT Unit Dependent
S1 Config Switch
(Read Circuit A)
R.CSA ConfigurationUNIT Unit Dependent
S1 Config Switch (Circuit B) C.SW.B ConfigurationUNIT Unit Dependent
S1 Config Switch
(Read Circuit B)
R.CSB ConfigurationUNIT Unit Dependent
S1 Config Switch (Circuit C) C.SW.C ConfigurationUNIT Unit Dependent
S1 Config Switch
(Read Circuit C)
R.CSC ConfigurationUNIT Unit Dependent
Air Cooled Reclaim Sel RECL ConfigurationUNIT NO†
DX Cooler Select DX.CL ConfigurationUNIT NO
Energy Management Module EMM Configuration
UNIT NO
Password Enable PAS.E ConfigurationUNIT ENBL
Factory Password PASS ConfigurationUNIT 0111
Cooler Heater Select CO.HT ConfigurationUNIT 1
Condenser Water Val Sel CON.V ConfigurationUNIT NO†
Hot Gas Bypass Select HGBP ConfigurationUNIT NO
MCHX Exchanger Select MCHX ConfigurationUNIT NO
High Tier Display Selec HI.TI ConfigurationUNIT NO
Hydronic Kit Select H.KIT ConfigurationUNIT NO†
Cooler Pass Number PA.NB ConfigurationUNIT 2
VLT Fan Drive Select VLT ConfigurationUNIT NONE†
VLT Fan Drive RPM RPM ConfigurationUNIT 0†
High Condensing Select H.CON ConfigurationUNIT NO†
Cooler Fluid Type FLUD ConfigurationSERV WATER
Condenser Fluid Type CFLU ConfigurationSERV WATER†
EXV MOP Setpoint MOP ConfigurationSERV 62
High Pressure Threshold HP.TH ConfigurationSERV 290.0