Operating instructions

CL-4
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Record Configuration Information
* Based on Navigator controls.
† Not supported.
TOUCH PILOT™ DESCRIPTION NAVIGATOR™
ITEM
NAVIGATOR
SUBMODE
DEFAULT* ENTRY
EXV A Superheat Setpoint SHP.A ConfigurationSERV Unit dependent
EXV B Superheat Setpoint SHP.B ConfigurationSERV Unit dependent
EXV C Superheat Setpoint SHP.C ConfigurationSERV Unit dependent
Cooler Heater Delta Spt HTR ConfigurationSERV 2.0 (Number of
degrees
added to brine
freeze
set point to enable
cooler heater.)
Entering Fluid Control EWTO ConfigurationSERV NO
Auto Start When SM Lost AU.SM ConfigurationSERV NO
Brine Freeze Setpoint LOSP ConfigurationSERV 34
Brine Flow Switch SP FL.SP ConfigurationSERV 1†
Varifan Proportional Gain HD.PG ConfigurationSERV 2.0
Varifan Derivative Gain HD.DG ConfigurationSERV 0.4
Varifan Integral Gain HD.IG ConfigurationSERV 0.2
Element CCNA ConfigurationOPTN 1
Bus CCNB ConfigurationOPTN 0
Baud Rate BAUD ConfigurationOPTN 9600
Circuit Loading Sequence LOAD ConfigurationOPTN EQUAL
Staged Loading Sequence LLCS ConfigurationOPTN AUTOMATIC
Ramp Loading Select RL.S ConfigurationOPTN DSBL
Unit Off to On Delay DELY ConfigurationOPTN 1
Ice Mode Enable ICE.M ConfigurationOPTN DSBL
Condenser Pumps Sequence† HPUM ConfigurationOPTN NO PUMP
Cooler Pumps Sequence PUMP ConfigurationOPTN NO PUMP
Pump Auto Rotation Delay ROT.P ConfigurationOPTN 48
Pump Sticking Protection PM.PS ConfigurationOPTN NO
Stop Pump During Standby P.SBY ConfigurationOPTN NO
Flow Checked if C Pump On P.LOC ConfigurationOPTN NO
Start Hour (Night Control) LS.ST ConfigurationOPTN 00.00
End Hour (Night Control) LS.ND ConfigurationOPTN 00.00
Capacity Limit (Night Control) LS.LT ConfigurationOPTN 100
Reverse Alarms Relay RV.AL ConfigurationOPTN NO
Heating OAT Threshold* OA.TH ConfigurationOPTN 5 F
Current Limit Select CUR.S ConfigurationOPTN NO
Current Limit at 100% CUR.F ConfigurationOPTN 2000
Cooling Reset Select CRST ConfigurationRSET NO RESET
Heating Reset Select HRST ConfigurationRSET NO RESET
Demand Limit Type Select DMDC ConfigurationRSET NONE
mA for 100% Demand Limit DMMX ConfigurationRSET 0.0
mA for 0% Demand Limit DMZE ConfigurationRSET 10.0
Master/Slave Select MSSL ConfigurationRSET DISABLE
Slave Address SLVA ConfigurationRSET 2
Lead/Lag Select LLBL ConfigurationRSET ALWAYS LEAD
Lead/Lag Balance Delta LLBD ConfigurationRSET 168
Lag Start Timer LLDY ConfigurationRSET 10
Start if Error Higher LL.ER ConfigurationRSET 4
Lag Minimum Running Time LAG.M ConfigurationRSET 0
Lag Unit Pump Control LAGP ConfigurationRSET OFF IF U STP
Lead Pulldown Time LPUL ConfigurationRSET 0
Chiller in Series SERI ConfigurationRSET NO